Configuration, Startup, and Operation 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
115 
4.3.20  Lock Out Parameter Set Up Group 
Introduction  
This is the parameter used to lockout any unauthorized changes to the recorder’s configuration, calibration, 
and pen alignment parameters. Calibration group functions are described in Section 5 – Input and Output 
Calibration for Recorder with Display.
 Pen alignment group functions are described in Section 8 – 
Troubleshooting and Pen Alignment for Recorder with Display.  
 
Set this group last  
Because this group contains functions that have to do with security and lockout, we recommend that you 
configure this group last, after all the other configuration data has been entered. 
 
Lockout group prompts 
Table 4-18 lists the function prompt in the lock out set up group. 
Press SETUP  key until “LOCK” appears in the lower display. 
Press FUNC  key to select the parameter. 
Table 4-18  Lockout Parameter Definitions 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
LOCK
 
 
 
LOCK
 limits access to one or more types of set up 
groups. Do not configure until all configuration is 
complete.
 
 
NONE       [factory setting] 
NO LOCKOUT
—All groups read/write. 
 
CAL 
CAL
—Locks out calibration and pen alignment groups; 
they will not even be displayed. All other groups are 
available for read/write. 
 
CONF 
CONF
—Tuning and cycle parameters are read/write. All 
other configuration groups (except lock) are read only. 
Calibration and pen alignment groups are not displayed. 
 
FULL 
FULL
— All configuration groups (except lock) are read 
only. Calibration and pen alignment groups are not 
displayed. 
 
ATTENTION 
The Lock function cannot be changed when the RUN/SETUP switch is in the "SETUP" position, making it 
usable as a physical lockout. Whatever lockout level is selected, it is protected as long as the switch is in 
the SETUP position.