Input and Output Calibration for Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
151 
5.5  Input Calibration Procedure 
Introduction 
Before performing this procedure, be sure the recorder is wired for calibration as described in Subsection 
5.4.  Apply power and allow the recorder to warm up for 30 minutes before you calibrate.  
Make sure “LOCK” is set to “NONE” (see Section 4 - Configuration, Startup and Operation of Recorder 
with Display). 
 
ATTENTION 
For Milliamp inputs, be sure the current source is at zero before switching on the calibrator.  
Do not switch the calibrator on/off while it is connected to the recorder’s input. Failure to observe 
this precaution could result in damage to input circuits. 
Calibration procedure sequence 
The calibration procedure sequence for all inputs is listed in Table 5-9. The calibration procedure for inputs 
1 and 2 is identical. The displays indicate the input number.   
Press the 
FUNC
  key to change display as required (INP1 or INP2).  
Table 5-9  Input Calibration Procedure Sequence 
Step Description 
Press 
Action/Result 
Enter Calibration Mode 
SET 
 UP
 
until you see 
  CAL
Upper Display
 
INPUT
Lower Display
 
 If “CAL” doesn’t appear or prompt access is declined, 
check “LOCK” configuration. 
 
 
FUNC
 
You will see: 
  DIS
Upper Display
 
CAL IN
Lower Display
   
 
 
 
The calibration sequence is enabled and you will see: 
  BEGIN
Upper Display
 
CAL IN
Lower Display