DR4300 Circular Chart Recorder Product Manual 
12/03 
A.2  Typical Reference Accuracy 
Table A-1  Typical Reference Accuracy 
Types of Input 
Actuations
 
Range
 
Reference 
Accuracy* 
with 
Field 
Calibration 
Factory 
Accuracy* 
 
Temp Stability 
± Degrees 
Error Per 1 Degree 
T
 
 
°F 
°C 
± °F 
± °C 
± °F 
± °C 
 
Thermocouples 
  
B 
 
105 to 3300
 
150 to 500 
500 to 1000 
1000 to 3300 
 
41 to 1816
 
66 to 260 
260 to 538 
538 to 1815 
 
 
28.0 
6.0 
3.0 
 
 
16.0 
3.3 
1.7 
 
 
 
37 
18 
 
 
 
21 
10 
 
 
4.00 
1.00 
0.40 
 E 
–454 to 1832 
–454 to –202 
–202 to 1832 
–270 to 1000 
–270 to –130 
–130 to 1000 
 
36.0 
2.0 
 
20.0 
1.1 
 
79 
14 
 
44 
 
1.40 
0.70 
 E 
(low) 
–200 to 1100 
–129 to 593 
1.0 0.6 11  6 
0.40 
 J 
0 to 1600 
–18 to 871 
1.6 0.9  7  4 
0.15 
  J (low) 
20 to 770 
–7 to 410 
0.8 0.5  6  3 
0.08 
 K 
–320 to 2500 
–196 to 1371 
2.4 1.4  9  5 
0.15 
 K 
(low) 
–20 to 1000` 
–29 to 538 
1.0 0.6  7  4 
0.10 
 Ni-Ni 
Moly 
32 to 2500 
32 to 500 
500 to 2500 
0 to 1317 
0 to 260 
260 to 1371 
 
1.5 
1.0 
 
0.8 
0.6 
 
12 
 

 
0.21 
0.14 
 Nicrosil-Nisil 
0 to 2372 
–18 to 1200 
2.1 1.2 11  6 
0.20 
 R 
0 to 3100 
0 to 500 
500 to 3100 
–18 to 1704 
–18 to 260 
260 to 1704 
 
4.0 
2.0 
 
2.2 
1.1 
 
26 
13 
 
14 
 
0.50 
0.21 
 S 
0 to 3100 
0 to 500 
500 to 3100 
–18 to 1704 
–18 to 260 
260 to 1704 
 
4.0 
2.0 
 
2.2 
1.1 
 
23 
13 
 
13 
 
0.50 
0.21 
 T 
–420 to 700 
–251 to 371 
1.6 0.9 13  7 
0.15 
 T 
(low) 
–200 to 600 
–129 to 316 
0.8 0.5  7  4 
0.15 
 W5W26 
0 to 4200 
0 to 600 
600 to 3600 
3600 to 4200 
–18 to 2316 
–18 to 316 
316 to 1982 
1982 to 2316 
 
2.8 
2.6 
3.2 
 
1.6 
1.5 
1.8 
 
19 
13 
27 
 
11 
15 
 
1.00 
0.50 
0.20 
RTD 
Platinum 
 100 
ohms** 
 100 
ohms 
(low)
** 
  100 ohms (T)*** 
 
 
–300 to 900 
–130 to 392 
–238 to 482 
 
 
–184 to 482 
–90 to 200 
–150 to 250 
 
 
0.8 
0.6 
0.6 
 
 
0.5 
0.3 
0.3 
 
 


 
 


 
 
0.15 
0.15 
0.15 
*Includes reference junction calibration of ± 0.01 degrees using the standard "ice bath" method of calibration. Factory accuracy at 
reference ± 1.2 °F.  Note that factory accuracy may have typical variations of ± 150 microvolts or ± 0.6 ohms for RTDs which 
means field calibration may be required to achieve stated accuracy. 
**IEC Alpha = 0.00385 
***Alpha = 0.00391