DCP200 Profile Controller & Recorder - Product Manual
Page 112
Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
10
Every 15 Minutes
11
Every 30 Minutes
Values To Display In 
Trend View
9001
0x2329
R/W
Value
Trend View Data
0
None (trend view off)
1
Process variable only
2
Process variable and setpoint
3
Process variable maximum & minimum 
since last sample
Profiler Control & Status Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Profile Run/Hold 
Signal
8192
0x2000
R/W
Value
Profile Run/Hold Signal Source
0
Operator Key Press Only
1
Digital input A
2
Digital input B
Profile Abort Signal
8193
0x2001
R/W
Value
Profile Abort Signal Source
0
Operator Key Press Only
1
Digital input A
2
Digital input B
Active Profiler 
Number
8243
0x2033
R/W
Currently selected profile number (1 to 64)
Active Segment 
Number
8244
0x2034
RO
Currently active segment (1 to 255)
Profiler Control 
Commands
8245
0x2035
R/W
Value
Profiler Command
0
Do nothing
1
Run the currently selected profile
2
Hold the currently running profile
3
Abort the currently running profile
4
Jump to the next segment
5
Release the hold
6
Exit profiler, return to controller mode
Note: The Profiler Control Commands must be followed by a Profiler Control Confirmation Action command.
Profiler Control 
Confirmation Action
8257
0x2041
R/W
Value
Implement Profiler Command
0
Do Not Implement Command
1
Implement previous Profiler Command
Enable Edit While 
Running
8262
0x2046
R/W
Value
Editing Current Running Profile
0
Editing current running profile forbidden
1
Editing current running profile allowed
Profile Control In 
Operation Mode
8260
0x2044
R/W
Value
Profile Control From Operation Mode
0
Operation Mode profile control disabled
1
Operation Mode profile control enabled
Profile Cycles Run
8247
0x2037
RO
The Number of times the currently running profile has 
cycled