Modbus Parameters
51-52-25-150, Issue 1 – April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Output 3 Retransmit 
Minimum
2211
0x08A3
R/W
Limited by input range maximum/minimum
Output 3 Retransmit 
Maximum
2212
0x08A4
R/W
Limited by input range maximum/minimum
Option Slot 4 Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Option Slot 4 
Module Type
2222
0x08AE
RO
Value
Module Fitted In Slot 4
0
None Fitted
1
Quad Relay
255
Error (unrecognised module)
Digital Output 4  
Status
2223
0x08AF
RO
Value
Digital Output 4A, 4B, 4C & 4D Status
0
All outputs inactive
Bit 0
Output 4A Active
Bit 1
Output 4B Active
Bit 2
Output 4C Active
Bit 3
Output 4D Active
Digital Output 4A 
Function
2230
0x08B6
R/W
Value
Digital Output 4A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Digital Output 4B 
Function
2231
0x08B7
R/W
Value
Digital Output 4B Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event