Honeywell NXL Benutzerhandbuch

Seite von 96
26(96) 
Installation 
Honeywell
Honeywell
Honeywell
Honeywell
 
 
 
C
A
NK5_2
D
B
A
B
 
 
5.2 
Cooling 
Forced air flow cooling is used for NXL HVAC and NXL Compact size MF3. 
 
Enough free space shall be left above and below the frequency converter to ensure sufficient air 
circulation and cooling. You will find the required dimensions for free space in the table below. 
 
 
 
Type 
Dimensions [mm] 
 
A 
NXL 0002-0006 2 
10 
10 
100 
50 
NXL 0001-0005 5 
10 
10 
100 
50 
HVAC 03-12 
20 
20 
100 
50 
HVAC 16-31 
20 
20 
120 
60 
HVAC 38-61 
30 
20 
160 
80 
 Table 5-4. Mounting space dimensions 
Figure 5-6. Installation space 
 
Type 
Cooling air required [m
3
/h) 
HVAC 03—12 
70 
HVAC 16—31 
190 
HVAC 38—61 
425 
Table 5-5. Required cooling air 
 
A 
= clearance around the freq. converter (see also B) 
= distance from one frequency converter to another or 
distance to cabinet wall 
C 
= free space above the frequency converter 
D 
= free space underneath the frequency converter