Cabling and connections 
Honeywell
Honeywell
Honeywell
Honeywell
 
 
 
6.1.4  Cable installation and the UL standards 
To meet the UL (Underwriters Laboratories) regulations, a UL-approved copper cable with a minimum 
heat-resistance of +60/75
°
C must be used. 
 
The tightening torques of the terminals are given in Table 6-6. 
 
Frame 
Tightening torque 
[Nm] 
Tightening torque 
in-lbs. 
MF2 
0.5—0.6 
4—5 
MF3 
0.5—0.6 
4—5 
MF4 
0.5—0.6 
4—5 
MF5 
1.2—1.5 
10—13 
MF6 
35 
Table 6-6. Tightening torques of terminals 
 
6.1.5  Cable and motor insulation checks 
 
1.  Motor cable insulation checks 
 
Disconnect the motor cable from terminals U, V and W of the frequency converter and from the motor. 
Measure the insulation resistance of the motor cable between each phase conductor as well as 
between each phase conductor and the protective ground conductor. 
 
The insulation resistance must be >1MΩ. 
 
2.  Mains cable insulation checks 
 
Disconnect the mains cable from terminals L1, L2 and L3 of the frequency converter and from the 
mains. Measure the insulation resistance of the mains cable between each phase conductor as well as 
between each phase conductor and the protective ground conductor. 
 
The insulation resistance must be >1MΩ. 
 
3.  Motor insulation checks 
 
Disconnect the motor cable from the motor and open the bridging connections in the motor connection 
box. Measure the insulation resistance of each motor winding. The measurement voltage must equal at 
least the motor nominal voltage but not exceed 1000 V. The insulation resistance must be >1MΩ.