Cabling and connections 
45(96) 
 
 
 
6.2.4  Control I/O 
 
 
 
Terminal 
Signal 
Description 
+10V
ref 
Reference output 
Voltage for potentiometer, etc. 
AI1+ 
 
Analogue input, voltage range 
0—10V DC.  
Voltage input frequency reference  
 
AI1- 
I/O Ground 
Ground for reference and controls 
AI2+ 
AI2-
/GND 
Analogue  input,  current  range 
0—20mA 
Current input frequency reference  
 
+24V 
Control voltage output 
Voltage for switches, etc. max 0.1 A 
7  GND 
I/O ground 
Ground for reference and controls 
DIN1 
Start forward (programmable) 
Contact closed = start forward 
DIN2 
Start reverse (programmable) 
Contact closed = start reverse 
 
10 
DIN3 
Preset speed selection 1 
(programmable) 
Contact closed = Preset speed 1 
11 
GND 
 
I/O ground 
Ground for reference and controls 
18 
AO1+ 
19 
AO1- 
Output frequency 
Analogue output 
Programmable  
Range 0—20 mA/R
L
, max. 500Ω 
RS 485 
Serial bus 
Differential receiver/transmitter 
RS 485 
Serial bus 
Differential receiver/transmitter 
30 
+24V 
24V aux. input voltage 
Control power supply backup 
 
21 
RO1 
22 
RO1 
23 
RO1 
 
Relay output 1 
FAULT 
Programmable  
Table 6-7. Default I/O configuration. 
 
Terminal 
Signal 
Description 
12 
+24V
 
+24 V DC 
Control voltage output; voltage for 
switches etc.  
13 
GND 
I/O ground 
Ground for reference and controls 
14  Exp DIN1  Preset speed selection 2 
(programmable) 
Contact closed = Preset speed 2 
15  Exp DIN2  Fault Reset 
(programmable) 
Contact closed = Fault reset 
 
16  Exp DIN3  Disable PID (PID control 
selection) 
(Programmable) 
Contact closed = Disable PID  
25  Exp RO1 
26  Exp RO1 
Expander Relay output 1 (NO) 
RUN 
Programmable 
28 
TI+ 
29 
TI- 
Motor Thermistor input 
Active = Fault, stop according to defined 
method 
Table 6-8. Additional inputs in NXL HVAC (available as option for NXL Compact) 
 
Terminal 
Signal 
Description 
+10V
ref 
Reference output 
Voltage for potentiometer, etc. 
AI1+ 
or 
DIN 4 
Analogue input, voltage range 
0—10V DC 
Voltage input frequency reference (MF2-3)  
Voltage/current input frequency reference 
(MF4-MF6) 
Can be programmed as DIN4 
AI1- 
I/O Ground 
Ground for reference and controls 
AI2+ 
AI2-
/GND 
Analogue  input,  voltage  range 
0—10V  DC  or  current  range 
0—20mA 
Voltage  or  current  input  frequency 
reference  
 
 
+ 24 V 
Control voltage output 
 
7  GND 
I/O ground 
Ground for reference and controls 
Table 6-9. AI1 configuration, when programmed as DIN4 
Reference 
Potentiometer 1-10 
 
 
mA