7.4.8  Modbus interface 
NXL has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance with 
the RS-485 standard.  
 
 
 
Protocol: 
 
 
Modbus RTU 
 
Baud rates: 
 
 
300, 600, 1200, 2400, 4800, 
9600, 19200, 38700, 57600 (bit/s) 
 
Signal level:   
 
RS-485 (TIA/EIA-485-A) 
Input impedance: 
 
2 kΩ 
 
7.4.8.1 
Modbus RTU protocol 
Modbus RTU protocol is a simple but effective fieldbus protocol. Modbus network has a bus 
topology, where every device has an individual address. With the help of the individual bus 
addresses the commands are directed to the single devices within the network. Modbus supports 
also broadcast -type messages, which are received by every device of the bus. Broadcast messages 
are sent to the address ’0’ which is reserved for these messages. 
 
The protocol includes CRC error detection and parity check for preventing the handling of messages 
containing errors. In Modbus the data is transferred in hex mode asynchronically and a break of 
approximately 3.5 characters is used as an end character. The length of the break depends on the 
used baud rate. 
 
Function 
code 
Function name 
Address 
Broadcast 
messages 
03 
Read Holding Register 
All ID numbers 
No 
04 
Read Input Register 
All ID numbers 
No 
06 
Preset Single Register 
All ID numbers 
Yes 
16 
Preset Multiple Register 
All ID numbers 
Yes 
Table 7-12. Modbus commands supported by NXL 
 
RS-485 Transceiver 
Control terminal 
RS-485 A 
RS-485 B 
Terminal resistor 120Ω  
X7 -> MF2-MF3 
X9 -> MF4-MF6