12.  NXL HVAC BASIC SPEED CONTROL – QUICK SETUP 
This chapter provides basic setup instructions for the user of NXL HVAC inverters, when using Basic 
Speed Control in HVAC applications. 
What you need to know 
  
Motor nameplate data 



 
Nominal current 



 
Nominal speed 
Speed signal specification 



 
Signal type (V, mA) 



 
Range (0-10, 2-10, 0-20, 4-20)  
 
 
 
 
 
 
Setup 
1  Run the Start-up Wizard 
Note:
 Running the Start Up Wizard resets all parameters to their default values. 
• 
Hold STOP button down for 5 seconds 
• 
Select application type FAN or PUMP and confirm with ENTER 
• 
Select motor nominal speed and confirm with ENTER 
• 
Select motor nominal current and confirm with ENTER 
• 
For speed signal 0 – 10 V use AI1 (Analogue Input 1) 
• 
All settings DONE 
2  Control Signal Settings for Speed Signals other than 0 – 10 V 
• 
For other selections full parameter view is needed: 
P2.1.14   
Parameter Conceal   
Set to 0 (not in use) 
 
• 
For speed signal 2 – 10 V use Analogue Input 1 
P2.2.6 
 
AI1 Signal Range 
 
Set to 4 (2 – 10 V) 
 
• 
For speed signal 4 – 20 mA use Analogue Input 2 
P2.1.15.14 
I/O Reference  
 
Set to 1 (AI2) 
 
• 
For speed signal 0 – 20 mA use Analogue Input 2 
P2.1.15.14           I/O Reference  
 
Set to 1 (AI2) 
P2.2.12              AI2 Signal Range 
 
Set to 1 (0 – 20 mA) 
 
Manual Test 
1  Hold LEFT down for 3-5 seconds 
Control Place automatically switches to Keypad 
2  Use normal keypad buttons for speed control 
• 
UP and DOWN to adjust the speed 
• 
START and STOP for control 
3  Hold LEFT down for 3 seconds to return to remote control (I/O or Fieldbus) 
 
Pump 
Fan 
or 
Load 
Pressure 
Sensor 
Control System 
Variable Frequency Drive 
Motor 
Speed Signal 
V signal to AI1 
mA signal to AI2