T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—09
4
Use a screwdriver to pry out only the knockouts that you 
will use. 
If mounting on DIN rail, be sure to remove the knockouts 
before mounting. See “Controller Wiring” on page 7 and 
Fig. 12 on page 9 for recommended knockout usage and 
locations. If you do not use an opened knockout be sure 
to cover it.
Mount the controller on any convenient interior location 
using the four mounting holes provided on the back of the 
enclosure using #6 or #8 screws (screws are not provided 
and must be obtained separately). Use controller 
dimensions in Fig. 1 on page 3 as a guide.
The controller may be mounted in any orientation. 
However, mounting in the orientation shown in Fig. 1 on 
page 3 permits proper viewing of the LCD display and use 
of the keypad.
Humidity, Pressure, and Universal 
Sensor(s) Mounting and Location
These sensors may be mounted on a wall or panel. Follow 
the installation instructions specific to the sensor you are 
installing.
Temperature Sensor(s) Mounting 
and Location
Temperature sensors may be located up to 1,000 feet 
(304 m) from the T775U controller. See Table 4 on 
page 11 for calibration guidelines.
The sensors may be mounted on a wall or panel for 
sensing space temperature, strapped to a pipe or inserted 
in an immersion well (see Fig. 2) for hot or cold water 
sensing, or taped to a standard cap or bulb holder for duct 
air sensing. To prevent moisture or condensation entering 
the sensor through the lead wire holes, mount the sensor 
with the lead wires exiting the bottom of the sensor.
NOTES:
1.
The included sensor is not designed for very 
wet applications. For immersion applications, 
an immersion well is used.
2.
Heat conductive compound must be used in 
immersion wells. 
3.
on page 2 for this type of installation.
Fig. 2. Sensor inserted in immersion well.
NOTE: Multiple sensors may be parallel-series wired 
to sense average temperatures in large 
WIRING
All wiring must comply with applicable electrical codes 
and ordinances, or as specified on installation wiring 
diagrams. Controller wiring is terminated to the screw 
terminal blocks located inside the device.
The remainder of this section describes the sensor wiring 
and the T775U controller wiring.
Wiring Connections Access
To access the wiring connections, remove the two screws 
on the left side of the enclosure and gently swing open the 
top. Be careful to not stress the ribbon cables that connect 
the keypad and LCD display to the controller circuit board.
Temperature Sensor Wiring
CAUTION
Electrical Shock Hazard.
Can short equipment circuitry.
Make sure that metal tube of sensor does not 
short against T terminals in wall-mounted case.
IMPORTANT
Poor wiring practices can cause erratic readings 
from the sensor. Avoid the following to ensure 
proper operation:
• Do not route the temperature sensor wiring with 
building power wiring.
• Do not locate the temperature sensor wiring next 
to control contactors.
• Do not locate the temperature sensor wiring near 
electrical motors.
• Do not locate the temperature sensor wiring near 
welding equipment.
• Make sure good mechanical connections are 
made to both the sensor and the controller.
• Do not mount the sensor with the lead wire end 
pointing up in an area where condensation can 
occur.
If any of the above conditions cannot be avoided, 
use shielded cable.
NOTE: Each T775 controller must be wired to its own 
sensor(s). However, a benefit of the T775 
controller’s accuracy is that there is no more 
than a 2°F differential between any two T775 
controllers.
Reset Temperature Control
If you are implementing two-sensor reset control, Sensor 
A must always be the controlled temperature and Sensor 
B must always be the controlling temperature. 
For example, in a reset control based on outside 
temperature, Sensor A must be the inside sensor and 
Sensor B must be the outside sensor.
Multiple Parallel Temperature Sensors
Multiple sensors can be parallel-series wired to sense 
average temperatures in large spaces. To maintain control 
accuracy, the number of sensors to be parallel-series 
wired must be of the n
2
 power (for example, 4, 9, 16, etc.). 
SENSOR
PLACED
IN WELL
IMMERSION
WELL
1/2 NPT
USE HEAT
CONDUCTIVE
COMPOUND
M24379