R7140G,L,M BURNER CONTROL MODULES
25
66-1153—03
1. In Pre-Purge Drive To High Fire Position (R7140L), the 
Run/Test Switch, when placed in the TEST position, 
holds in PREPURGE with the firing rate motor in the 
High Fire position.
2. In the measured PREPURGE sequence, the Run/Test 
Switch, when placed in the TEST position, causes the 
PREPURGE timing to stop. The firing rate motor is in 
the High Fire position.
3. In Pre-Purge Drive to Low Fire position, the Run/Test 
Switch, when placed in the TEST position, holds the 
burner sequence in PREPURGE with the firing rate 
motor in the Low Fire position.
4. In PFEP, the Run/Test Switch, when placed in the TEST 
position, stops the timer during the first 8 seconds when a 
10-second PFEP is selected or during the first 3 seconds 
when a 4-second PFEP is selected, allowing pilot-turn-
down test and other burner adjustments to be made. This 
activates a 15-second flameout timer that permits pilot 
flame adjustment without nuisance safety shutdowns. The 
Run/Test Switch is ignored during PFEP for the R7140L if 
terminals 5 and 7 or 7 and 6 are jumpered.
5. During Run, the Run/Test Switch, when placed in the 
TEST position, drives the firing rate motor to the Low 
Fire position.
NOTE: When R7140 is switched to the Test mode, it stops 
and holds at the next Run/Test Switch point in the 
operating sequence. Make sure that the Run/Test 
Switch is in the RUN position before leaving the 
installation.
SETTINGS AND ADJUSTMENTS
Selectable Site-Configurable 
Jumpers
The R7140 has three site-configurable jumper options; see 
Fig. 19 and Table 7. If necessary, clip the site-configurable 
jumpers with side cutters and remove the resistors from the 
Relay Module.
The R7140M has two additional jumpers located on the back 
of the chassis. These must be cut if a spring return damper 
motor is used.
Fig. 19. Selectable site-configurable jumpers.
Table 7. Site Configurable Jumper Options.
a
Pilot Valve/First Stage Oil Valve (Valve/Start) terminal 6.
b
A 30 second MFEP can be accomplished by adding a jumper wire between terminals 15 and 8.
SERVICE NOTE: Clipping and removing these site-configurable jumpers enhances the level of safety. Removal after 200 hours of 
main valve operation will result in a hard lockout, Code 110.
RUN/TEST SWITCH
NOTE:  CONFIGURATION JUMPERS SHOWN FOR RM7800G/RM7840G.
SELECTABLE CONFIGURATION JUMPERS
M12301
Jumper Number
Description
Intact
Clipped
RM7800/RM7840 Type
JR1
Pilot Flame Establishing 
Period (PFEP)
10 seconds
4 seconds
All
JR2
Pilot Valve
a
/Main Flame 
Establishing Period (MFEP)
10 seconds
Intermittent
15 or 30 seconds Interrupted
b
R7140G
JR3
Start-up Interlock Check
Disabled
Enabled
All