Part # 25000102
Installation and Operations Manual
Figure 2. Vibration Pad Locations
System Warranty
This equipment is designed to operate properly and produce 
the rated capacity when installed in accordance with good 
refrigeration practice.
The following conditions should be adhered to when installing 
this unit to maintain the manufacturers warranty:
(a)  System  piping  must  be  in  accordance  with  good 
refrigeration practices
(b)  Inert  gas  must  be  charged  into  the  piping  during 
brazing
(c) The power supply to the unit must meet the following 
conditions:
• All voltages must be +/- 10% of the  n a m e p l a t e 
ratings
• Phase (voltage) imbalance cannot exceed 2%
(d) All control and safety switch circuits must be properly 
connected according to the wiring diagram
(e) The factory installed wiring must not be changed without 
written factory approval
Rigging
Warning: Careful considerations for lifting should be made 
before the unit is lifted by any means. The only part of the unit 
designed to carry any of the lifting load is the welded channel 
base. The unit may be lifted at the base with a forklift or by 
means of cables at the four corners of the base. If cables are 
used, the lifting cables should be prevented from contacting 
any of the unit piping or electrical components.
Location Of Equipment - Indoor
Clearances
The parallel systems should be located so they are level and 
easily serviced. The minimum suggested clearance around 
the units should be 24 inches at the rear and 42 inches in the 
front of panel (or as required by National or Local Codes). For 
parallel system units placed end to end, 24 inches between 
units is suggested.
Floor & Foundation Requirements
 
The total weight of a single unit will vary between 1200 pounds 
and 10,000 pounds. Allowances must be made for the parallel 
rack and all other equipment installed in the same area as the 
parallel units. The location and installation of all equipment 
should  be  in  accordance  with  all  local  and  national  code 
requirements.
While each unit is constructed with a welded steel base frame 
adequately  designed  to  withstand  vibration,  the  natural 
pulsating action of the interconnected motor-compressors 
may cause considerable noise and vibration if the unit is not 
mounted on a firm level surface and isolated from the structure 
of the building.
Vibration Mounts
In ordinary ground level or basement installations, all that is 
necessary to assure a vibration-free installation is to place the 
unit on the concrete floor with the waffle-surfaced resilient pads 
supplied. See Figure 2 for suggested pad locations. Mezzanine 
and other installations require some special considerations. 
The equivalent of 6 inch thick properly reinforced concrete 
floor  must  be  provided  for  mounting  parallel  units  above 
grade.  It  is  recommended  that  the  suggestions  previously 
given for rigid floor construction on above-grade installations 
be closely adhered to. If this is not possible, special vibration
NOTE: Turn each leveling nut until the tip casting 
rises  1/4”  to  3/8”  above  the  bottom 
casting. MOUNT ADJUSTMENT SHOULD 
NEVER EXCEED 3/4”.
Figure 1. Vibration Pad and Spring Isolator