Editing Sensor Parameters
5.
If the detected new sensor is not the same type as the replaced sensor, the 
INVALID SENSOR TYPE screen is displayed. Press OK (F3) to return to the 
SENSORS screen:
6.
Do one of the following: 
Replace the physical sensor with one that matches the type of the 
replaced sensor and repeat this procedure.
Delete the sensor from the base unit and replace with the new sensor (of a different type). See “Deleting 
7.
If you wish to replace another wireless sensor, repeat this procedure.
8.
If you are finished performing sensor maintenance, press 
 to exit maintenance and resume monitoring.
9.
Press F1 to lock the keypad.
Editing Sensor Parameters
The general procedure for editing sensor parameters is provided below. Not all sensor parameters can be edited 
for an installed sensor. The editable parameters are dependent on the installed sensor, so the 
EDIT SENSOR screen 
varies according to the sensor selected. You cannot edit the following:
The low and high scaled values for a 4-20mA sensor. If these require changes, you must delete the 4-20mA 
sensor and re-add it to the system. See “Connecting Wired HA-III+ Humidity Sensors” on page 25.
A sensor’s type. For example, if a 4-20mA sensor was incorrectly added as a Blue temperature sensor, you 
must delete the incorrect sensor and then re-add the correct sensor.
The unit of measure. If unit of measure must be changed, the sensor must be deleted and re-added to the system.
Note:
Update the system’s Configuration Worksheets to document changes.
F3
F1
Select the sensor to edit.
Select the parameter to be edited.
Use PREV, NEXT, and arrow keys to change value 
as required.
To edit another 
parameter
when done 
editing
to lock