Appendix A.5.1. 
FieldServer Configuration File  
The configuration file used for this example is configured with the following Connection, Node and Map Descriptor Parameters: 
 
//    Data Arrays 
 
 
// 
 
 
Data_Arrays 
 
 
Data_Array_Name   ,Data_Format   ,Data_Array_Length 
DA_Read          
,Float        
,100 
DA_Write         
,Float        
,100 
 
//    Server Side Connections 
// 
 
 
Connections   
 
Adapter  
,Protocol     
,Turnaround_delay 
N1       
,Ethernet/IP   ,0.01s 
 
//    Server Side Nodes   
// 
 
Nodes 
 
Node_Name  
,Protocol 
EIP_01     
,Ethernet/IP 
 
//    Server Side Map Descriptors 
 
 
 
// 
 
 
 
 
 
 
 
Map_Descriptors 
 
 
 
 
 
 
 
Map_Descriptor_Name   ,Data_Array_Name   ,Data_Array_Offset   ,Node_Name   ,Function  ,EIP_SERVICE       
,EIP_TAG_NAME   ,Length 
FS_TO_PLC_DATA       
,DA_Read          
,0                  
,EIP_01     
,Server   
,DATA_TABLE_READ    ,Read_Data     
,20 
PLC_TO_FS_DATA       
,DA_Write         
,0                  
,EIP_01     
,Server   
,DATA_TABLE_WRITE   ,Write_Data    
,20 
Number of data points made available 
for reading or writing within the Tag. 
 “FieldServer “Tag names that will be called in the PLC Message Block.  The 
names must match what is written in the Message block in the PLC exactly. 
Note: The corresponding PLC Tag Name can be different and probably will 
be.  See Message Block Below.