Parameter 
Description 
external device trying to access it. 
Msg Ignored 
Messages received but unable to be processed - normally
because the driver has not implemented functionality for that 
message.
 
Sys Cleared 
The number of times that Data Arrays were cleared after a 
system-normal type message was received from a device (e.g.
fire alarm panel) 
Squelch TX
2
 
The number of bytes received during the squelch timing period 
started when RTS is asserted. 
Squelch RX
The number of bytes received during the squelch timing period 
started when RTS is de-asserted. 
Cache Failed 
FieldServer unable to create a cache block due to memory 
shortage or inability to find a downstream node.   
Segmentation Not Supported 
The received message was segmented but the driver does not 
support re-assembling segmented messages. 
Passthru Retries
3
 
Produced when a Passthru poll is busy on the downstream side, 
and an identical poll (retry) is received on the upstream side. 
Passthru Overruns
Produced when a Passthru poll is busy on the downstream side 
and a different poll (not a retry) is received on the upstream side. 
Passthru Early Retries 
A Passthru Retry, which occurs when the upstream retry is 
received before the 1
st
 downstream Passthru poll has been sent. 
Passthru Normal Retries 
A Passthru Retry, which occurs when the upstream retry is 
received after the 1
st
 downstream Passthru poll has been sent. 
Passthru Early Overruns 
A Passthru Overrun, which occurs when the upstream retry is 
received before the 1
st
 downstream Passthru poll has been sent. 
Passthru Normal Overruns 
A Passthru Overrun, which occurs when the upstream retry is 
received after the 1
st
 downstream Passthru poll has been sent. 
Passthru Early Overruns Fails
Passthru Normal Overruns 
Fails 
This statistic is currently not used. 
PWT Expired 
The Passthru Window Timer expired before the downstream 
Passthru poll could be sent. 
 
2.3.5. 
Connection Overview - API Aspect 
These statistics are produced by the FieldServer kernel’s API (Application Programmer 
Interfaces).  They are intended for advanced users only. 
 
Press the 1 key or the 2 key to change the filter on these stats. 
1 = TCP API 
2 = Ethernet API (Default) 
 
                                                 
2
 
Information is available in ENOTE19. Enotes are available on the Web at www.fieldserver.com. 
3
 Currently only produced by the Metasys driver