Terminal Position
POSITION
MINIMUM SPACING
mm
A
Directly below an openable window, air vent, or any other ventilation opening
300
B
Below gutters, soil pipes or drainpipes
75
C
Below Eaves
100
D
Below a Balcony
100
E
From vertical drainpipes or soilpipes
75
F
From internal or external corners
100
G
Above adjacent ground or balcony level
100
H
From a surface facing the terminal
600
I
Facing another terminal
1,200
J
From opening (door/window) in carport into dwelling
1,200
K
Vertically from a terminal on the same wall
300
L
Horizontally from a terminal on the same wall
300
N
Below carport
600
A Quinnel Barrat and Quinnel guard (part. No. C2) should be screwed to the wall centrally over the terminal,  when
the  terminal height is less than 2 m from floor level.
Fig. 12
CLEARANCES:
* 600mm minimum clearance for servicing
access
460
5 min.
5 min.
100 min.
860
200 min.
270
50 mm
600* min.
720
Fig. 11