Carrier WEATHERMAKER INFINITY 58MVP Benutzerhandbuch

Seite von 48
NOT ENOUGH COOLING AIRFLOW—Generally, this indicates the Y/Y2 thermostat lead is not properly
connected.
STEP
ACTION
YES
NO
GO TO
1.
Remove blower access panel and depress door switch. Use a piece of tape to hold switch closed.
Wait a few sec for self test before proceeding to next step.
2
2.
Make sure thermostat is calling for cooling. If thermostat lead G is not connected, jumper across
thermostat terminals R and G.
3
3.
Make sure thermostat fan control is in AUTO position if equipped.
4
4.
Do you have 24v across Y/Y2 and Com on furnace control board?
8
5
5.
You have a defective thermostat, or a break in wiring between thermostat and furnace, or the Y/Y2
thermostat terminal is not wired to thermostat.
6
6.
Fix problem.
7
7.
Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS.
INDEX
8.
Are air conditioning select switches A/C set to proper tonnage as required by condensing unit? (See
Table 1.)
10
9
9.
Set air conditioning select switches A/C for proper tonnage as required by condensing unit. (See
Table 1.)
7
10.
Disconnect the G thermostat lead or jumper if used.
11
11.
Does blower motor turn off in 90 sec when G thermostat lead is disconnected?
12
13
12.
Replace furnace control board.
7
13.
Observe operation of furnace in cooling mode for 8 minutes.
14
14.
Does furnace operate properly in cooling mode?
15
16
15.
Make sure outdoor unit is properly charged. If it is, go to page number indicated in Index for
CLEANUP AND START-UP INSTRUCTIONS. If problem persists on an intermittent basis, replace
furnace control board. If problem still persists after replacing furnace control board, contact your dis-
tributor.
INDEX
16.
Does furnace abruptly go through a self-test sequence as blower comes up to speed?
17
24
17.
Do you have less than 17 vac between R and Com on furnace control board?
18
24
18.
Do you have less than 90 vac between P1 and P2 on furnace control board?
19
20
19.
Make sure the wire gage between main fuse box and furnace complies with wire size specification
in Installation, Start-Up, and Operating Instructions.
6
20.
Disconnect the R thermostat lead.
21
21.
Do you have less than 17 vac between R and Com on furnace control board?
22
23
22.
Replace transformer.
7
23.
Check the thermostat wire gage between furnace and thermostat, and furnace and outdoor unit. It is
recommended that AWG No. 18 color-coded copper thermostat wire be used for lengths up to 100
ft. For wire lengths over 100 ft, use AWG No. 16 wire.
6
24.
Press down on microprocessor chip and make sure it is properly seated to furnace control board. If
it is, replace furnace control board.
6
Table 1—Air Conditioning (A/C) Airflow Setup Switch Position
AIR CONDITIONER
(TONS)
AIRFLOW
(CFM)
A/C SWITCH POSITION
ALLOWABLE FURNACE MODEL SETUP
A/C-1
A/C-2
A/C-3
040
060
080
080
100
120
Default
1200 or
2000
OFF
OFF
OFF
3 Tons
1200 CFM
3 Tons
1200 CFM
3 Tons
1200 CFM
5 Tons
2000 CFM
5 Tons
2000 CFM
5 Tons
2000 CFM
1-1/2
600
ON
OFF
OFF
X
X
X
2
800
OFF
ON
OFF
X
X
X
X
X
X
2-1/2
1000
ON
ON
OFF
X
X
X
X
X
X
3
1200
OFF
OFF
ON
X
X
X
X
X
X
3-1/2
1400
ON
OFF
ON
X
X
X
X
X
X
4
1600
OFF
ON
ON
X
X
X
5
2000
ON
ON
ON
X
X
X
X—Indicates allowable selection.
10