Protect PV.500-MH Operating Instructions 
44 of 68 
80000043212 BAL 
 
7.1.3  Structure of the  MultiCom CCC Interface 
1
1
1
1
1
1
1
1
X3
X1
X2
X4
X5
J1
J5
J4
LED
gn
rt
S1
RS232:
RS485:
B  A  B  A
 
              Modbus               Configuration 
Figure 13 
MultiCom CCC interface as a Modbus interface (top view)  
Connections: 
X1:  
Internal inverter bus and power supply 
X2:  Potential-free RS232 serial interface 
X3:  Triggering of "Remote signalling" 
X4:  A remote panel can be connected to this potential-free CAN 
interface.  
X5:  Potential-free RS485/RS232 serial interface internally wired 
to X91 
 
Configuration jumpers: 
J1:
  
1-2: Firmware update;         2-3: (default) 
J4: 
All closed:             RS485 (default
J5:  
All closed:             RS232 
 
The transmission topology of the Modbus interface (connector X5) 
is set by means of the two configuration jumper blocks (J4/J5). The 
factory setting is RS485. 
In order to be able to use the Modbus interface as a point-to-point 
connection via RS232, you must remove all jumpers from block J4 
and plug them in on block J5. 
 
Button: 
S1:  
Button for initiating the configuration via connector X2