Configuring the MES1A/B 
Manual Documentation Number: MES1A/MES1B-2106m        PN7138-rev001 
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com 
B&B Electronics Ltd – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com 
     28
 
MES1B for RS-485 two-wire operation, the CP1 parameter must be set for 
RS485 Enable to ensure Send Data Control is implemented. 
No configuration is required in this section for MES1A converters. 
To configure RS485 Enable in the Modem/Configurable Pin Settings 
section: 
33.   Type  3 at the 
Select Command or parameter set (1..4) 
to change: 
prompt. The 
CP1 Function
 prompt appears. 
34.  Type 4 to select RS485 Enable 
35.  To accept the change, press Enter 
36.  Press  Enter three more times to exit the Modem/Configurable Pin 
Settings section of the Configuration Menu. 
4) Advanced Modbus Protocol Settings 
In the Advanced Modbus Protocol Settings section of the Configuration 
Menu you can configure: 
•  whether the Slave Address is fixed or used as received 
•  whether to Allow Modbus Broadcasts 
•  whether to Use MB/TCP 00BH/00AH Exception Responses 
•  whether to Disable Modbus/TCP Pipeline 
•  Character Timeout values 
•  Message Timeout values 
•  Serial TX delay after RX values 
•  whether to Swap 4x/0H to get 3x/1x register conversions 
 
Figure 18. 
Advanced Modbus Protocol Settings Menu