Configuring the MES1A/B 
Manual Documentation Number: MES1A/MES1B-2106m        PN7138-rev001 
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104 – www.bb-elec.com 
B&B Electronics Ltd – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445 – www.bb-europe.com 
     32
 
Serial TX Delay after RX 
When the MES1A/B receives a request from a master it relays the request to 
the Modbus slave connected to the MES1A/B’s serial connection. When the 
slave responds a timer is triggered and, after the delay time configured in the 
Serial TX Delay after TX field, the next master request is allowed to pass 
through the serial connection to the slave. When using 2-wire RS-485 
connections, this delay value can be set to ensure that RS-485 devices have 
time to disable their drivers and enable their receivers to receive the next 
request. Typically this is not a concern and the default value is 0. The delay 
can be set to a maximum of 1275 milliseconds. 
Swap 4x/0H to Get 3x/1x 
This field allows you to configure the MES1A/B to convert holding register 
(4x) data to input register (3x) data, and convert coil (0x) data to contact (1x) 
data. This is useful when connecting to Modicon I/O scanners. 
5) Unit ID to IP Address Lookup Table Settings 
The  Configuring Unit ID to IP Address Table Settings section of the 
Configuration Menu becomes available if the MES1A/B has been configured 
as a Modbus Master in Configuration Menu section 2).  
From Configuration Menu section 5) you can configure: 
•  whether to Close Idle TCP Sockets after a specified number of seconds 
•  whether to enable Redundant entry retries after a specified number of 
seconds 
•  the Unit ID to IP Address Lookup Table 
 
Figure 19. 
Unit ID -> IP Address Table Settings Menu 
Close Idle TCP Sockets After 
The 
Close Idle TCP Sockets After
 field allows you to configure 
whether a socket is held open, or the number of seconds to hold the last 
socket open.