GDA-1600 16-Channel Controller 
17 
3.2.4.2  Marker Menus 
Some transmitters/monitoring devices providing GDA-1600 inputs also indicate special 
modes of operation (such as Calibration, Maintenance or Fault) by transmitting a special 
<4mA  or negative “Marker” value.  The GDA-1600  offers  channel  Marker menus  for 
detecting  and indicating such events  (see  Figure 3.5).  While  active, the GDA-1600 
displays a 6-digit ASCII message to indicate the special event and if equipped with the 
4-20mA output option (P/N 5700-0005), the GDA-1600 also transmits the same <4mA 
value. 
 
Figure 3.5 – Marker Menus 
 
Entries 
Description 
Marker Enabled  Marker Enabled turns the marker feature ON and OFF 
Marker % 
The negative Marker value is entered into the Marker % field as a negative percent 
of the full scale.  For example, -15.62% of full scale detects a marker value of 1.5mA 
(1.5mA is -15.62% of full scale when 4-20mA is the range). 
Mark As 
The Mark As menu allows user entry of the 6-digit ASCII message to be displayed 
when the marker is detected. 
 
3.2.4.3  Sensor Life Detection 
Sensor Life should only be activated when the Marker event is Calibration and when a 
sensor life value is transmitted after each calibration.   
NOTE: This feature is provided primarily for use when interfacing with the GDA-1600 
to  Bacharach’s  GDX-350  Sensor Transmitters  which  may be configured to 
transmit sensor life values after each calibration (see Figure 3.6).   
Entries 
Description 
Sensor Life 
For Sensor Life to record properly, the monitor must perform as follows:  After the 
Calibration  Marker interval, 4.0mA transmits for 10 seconds to indicate its 
calibration mode is complete.  The monitor then transmits between 4.0mA and 
5.0mA for five seconds depending on remaining sensor life, where 4.0mA = 0% and 
5.0mA = 100% remaining sensor life.  The GDA-1600 reads this value and records it 
as the channel’s Sensor Life.  Sensor Life  is stored in the GDA-1600  Modbus 
database and displayed as a bar-graph in the Sensor Info screen (see section 3.3.6 
on page 25).  It is a useful tool for planning sensor replacement schedules. 
Reset Sen. Life