Bradley Smoker PLC-5 Benutzerhandbuch

Seite von 388
Publication 1785-UM012D-EN-P - July 2005
E-4        Switch Setting Reference
I/O Chassis Backplane
PLC-5 Controller in the I/O Chassis
      Regardless of this switch setting, outputs are turned off when any of the following occurs:
processor detects a major fault
an I/O chassis backplane fault occurs
you select program or test mode
you set a status file bit to reset a local rack
      If a memory module is not installed and processor memory is valid, the processor’s PROC LED
   indicator blinks, and the processor sets S:11/9 in the major fault status word.  Power down the processor
   chassis and either install the correct memory module or set switch 6 ON.
      If the processor’s keyswitch is set in REMote, the processor enters remote RUN after it powers up and has
   its memory updated by the memory module.
      You cannot clear processor memory when this switch is on.
4
5
2 - slot
1 - slot
1/2 - slot
1
A lways
O ff
19309
6
7
Outputs of this I/O chassis remain in their last state when
a hardware failure occurs. 
Outputs of this I/O chassis are turned off when a 
hardware failure occurs. 
Pressed in 
at top ON (closed)
Pressed in 
at bottom OFF (open)
memory module transfer to processor memory at powerup. 
memory module transfers to processor memory if processor memory
not valid.
memory module does not transfer to processor memory. 
Processor memory protection disabled.
Processor memory protection enabled. 
Not allowed
Processor Memory Protection
Switch
off
on
Memory Module Transfer
Addressing
Last State
Switch
on
off
Switches
Switches
off
off
off
on
on
off
on
on
off
off
on
on
on
off
8
2
1
3
4
2
1
3
4
1