D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 11 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
2.0 GV2MAIN 
Use GV2MAIN programming module to define the 
operating characteristics that affect panel-wide 
functions. This module has nine programming 
categories:  
 
• 
• 
• 
• 
• 
• 
• 
• 
• 
Phone 
Phone Parameters 
Routing 
Enhanced Communications 
Area Parameters 
Keypad 
User Interface 
Function List 
Relay Parameters. 
2.1 Phone 
The control panel can dial as many as four different 
telephone numbers when sending event reports. All 
telephone numbers use the same receiver format. 
Refer to Section 2.3 Routing on page 15 for 
information about event report routing and 
communication protocols. 
 
 
When using PSTN telephone lines, 
program two telephone numbers to 
meet UL 864 requirements. 
Phone 1 
Default: 
Blank 
Selection:  Up to 24 characters (do not enter 
[SPACE]) 
0 to 9 
Numbers 0 through 9 
C 3-sec 
pause 
7-sec dial-tone detection 
# or * 
Used for the same purpose as 
pressing this key on a telephone 
keypad when manually dialing. For 
example, an asterisk (*) may be 
needed to access your long distance 
service. Do not use these characters 
when pulse dialing. 
Blank 
Control panel dials no phone number. 
Programming this item Blank does 
not disable phone routing. To disable 
reporting to this phone, refer to 
Section 2.3 Routing on page 15. 
This is the telephone number the control panel dials 
to contact the central station receiver when sending 
event reports. This number is Phone 1 referred to in 
the prompts in Section 2.3 Routing on page 15. 
The control panel is programmed with a 7-sec dial 
tone detect period. When a dial tone is detected or 
the waiting period ends, the control panel begins to 
dial. To extend the dial tone detect period, place a D 
before the phone number. To insert a pause during or 
after dialing, use C in the number sequence. For 
example, if the control panel hangs up before it hears 
the Modem IIIa
2
 ACK tone from the D6500 or D6600, 
program extra Cs after the phone number. The 
control panel waits on line for three extra seconds for 
each C programmed. 
Enter up to 24 of the characters shown in the Phone 
1
 table to define dialing characteristics. 
 
Using both phone-data entry lines: The 
first line of the phone number data entry 
line must be filled (twelve characters) 
before you press [ENTER] to move to the 
second line. If you enter characters on 
the second line, and the first line has less 
than twelve characters, the second line 
clears when you press [ENTER]. 
For SIA CP-01 Compliance 
Call Waiting Disable 
If the telephone system at the installation site uses 
the Call Waiting feature, ensure that the backup 
telephone reporting number is programmed to 
disable Call Waiting.  
If you program the primary phone number with a 
sequence to temporarily disable Call Waiting 
(typically *70 pause, but verify with the phone service 
provider) followed by the phone number, you should 
program the backup phone number without the Call 
Waiting cancel sequence. If the subscriber cancels 
Call Waiting without notifying their alarm installing 
company, the control panel can still send reports 
using the backup number.  
 
Dialing a Call Waiting sequence on a 
non-Call Waiting line prevents the system 
from dialing the central station receiver 
successfully. 
 
 
Example: If the central station telephone 
number is 555-1234, and the backup 
Route Group destination is Phone 2, 
program Phone 2 with the following 
sequence: 70C5551234