D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 38 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
Points programmed for instant alarm 
 
A# FA Bypass Max 
response generate alarms immediately, 
Default: 
even during exit delay. To avoid instant 
alarms on points adjacent to the 
Selection:  0 to 99 
perimeter when leaving the area, 
program P## Type as 3 (Interior 
Specify the maximum number of combined 
Controlled points that can be faulted or bypassed 
when arming this area. 
Follower). 
For SIA CP-01 Compliance 
Refer to the prompts P## FA Retrnable and P## BA 
Retrnable
 in Section 
The Exit Delay Time must be between 45 sec and 
255 sec. 
4.2 Point Responses on page 
92 for returning a point to the system when the point 
returns to normal or when the area is disarmed. 
 
A# Auto Watch 
 
 
Users can bypass more points than the 
number entered here during the 
disarmed state. It is only when the user 
attempts to Bypass Arm an area (or 
areas) that this restriction is enforced. 
Default: 
No 
Selection:  Yes or No 
Yes 
When the area is disarmed, Watch 
Mode turns on automatically. 
A# Delay Res 
No 
When the area is disarmed, Watch 
Mode must be turned on or off 
manually. 
Default: 
No 
Selection:  Yes or No 
 
Controlled points must be programmed 
Yes 
Point Restoral Report is not sent until 
the bell time expires or user 
acknowledges alarm condition. 
as P## Watch Point to generate a 
watch tone. 
 
No 
Restoral Reports are sent when point 
restores, regardless of bell time. 
A# Verify Time 
Default: 
60 
A# Exit Tone 
Selection:  10 to 60 (in 1-sec increments) 
Default: 
Yes 
Use alarm verification with smoke detectors to reduce 
the number of false fire alarms. When Verify Time is 
programmed, the control panel can check smoke 
detector point activations before generating alarm 
signals. 
Selection:  Yes or No 
Sounds an exit tone during exit delay at all keypads 
assigned to this area. 
 
You can turn off exit tones for individual 
keypads by programming the 
appropriate CC# 1 to 8 as No in CC# 
Exit Tone
A# Exit Dly Time 
Default: 
60 
Selection:  Blank (0) to 600 ( in 5 sec 
increments) 
Exit delay time for this area when Master Exit or 
Perimeter Exit arming. 
 
 
•  Do not enable the Cross Point feature 
in point indexes designated for Fire 
points. 
 
•  Check with your authority having 
jurisdiction (AHJ) to determine the 
maximum verification time allowed. 
Points are programmed individually to activate the 
verification feature. Refer to Section 4.1 Point Index 
on page 88. Any resettable Fire point can activate 
alarm verification for the area to which it is assigned. 
Use separate area alarm-verification relays. 
To enable alarm verification on a point, program 
Point Index, Fire Point, Alarm Verify, and Resettable 
as Yes