D9412GV2/D7412GV2 | Program Entry Guide | 4.0  RADXPNTS 
EN | 97 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
P## RlyResp Type 
P## Disp as Dvc 
Default: 
Refer to the program record sheet 
Default: 
No 
Selection:  Blank, 1 to 2 
Selection:  Yes or No 
Blank 
Point state does not affect the 
operation of the corresponding relay. 
Display CHECK DEVICE when this 
point is off-normal. 
Yes 
Relay Follows Point: The relay 
corresponding with this point 
activates when the point is faulted to 
any off-normal condition, even if the 
point is bypassed. The relay 
automatically resets when the point 
returns to normal. 
Do not display CHECK DEVICE 
when this point is off-normal. 
No 
Use P## Disp as Dvc to cause the keypad to display 
CHECK DEVICE when a point is off-normal or is 
acknowledged after going into alarm. 
Relay Latches: The relay 
corresponding with this point latches 
when the point enters into an alarm 
condition. This relay provides a 
steady output until the alarm is 
acknowledged by a valid pass code, 
then cleared from alarm memory with 
an acknowledgment from the keypad. 
Use this option to cause a relay (1 to 127 for 
D9412GV2; 1 to 64 for D7412GV2) to respond when 
a corresponding point with the same number (1 to 
127) is faulted. This requires connecting D8129 
OctoRelays to Zonex Bus 1 and Zonex Bus 2 
(D9412GV2 only). Refer to the address settings on 
the back of the D9412GV2/D7412GV2 Program 
Record Sheet  
(P/N: F01U003635). 
 
 
Point 128 is reserved for use other than 
an actual point. Only the first 127 points 
can have an associated relay. Relays are 
not available for Points 129 to 247. 
 
 
 
Do not use the Chg Relays? function to 
toggle relays reserved for special 
functions. Special function relays are 
Area and Panel Wide Relay functions as 
well as relays assigned to CC Entr Key 
Rly and P## RlyResp Type
 
Use this function for devices with a dry 
contact output that faults a point when 
the device is in a trouble condition. 
 
P## Local While Disarmed 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
Suppress Alarm, Trouble and 
Restoral* Reports from this point 
while the area to which it is assigned 
is disarmed. 
Yes 
Send event reports occurring from 
this point while the area is disarmed. 
No 
*  Transmission of Restoral Reports continues if the alarm, 
trouble, or bypass (by Sked, RPS, or Swinger bypass) 
condition occurred when the area disarmed, and the point 
restored. 
 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, set this parameter to No
Use this option to allow a Controlled point (P## Type 
1, 2, 3
), to report Alarms, Troubles, and Restoral 
Reports only when the area is armed. This prompt 
does not affect local annunciation.