BLACKHAWK! Power Supply Blackhawk Series Broadband Power Supplies Benutzerhandbuch

Seite von 31
Section 10:   Specifications  
 
 
Black Hawk 600-120/60-36  or 600-120/60-48   
 
AC Input Voltage ………………………  120 volts AC, nominal 
Nominal Input Voltage Tolerance ..…  ±10% (108-132 volts) 
AC Input Current ………………………  6 amps, nominal 
Input Frequency ………………………..  60, ± 3 Hz 
Line Reject Value ………………………  95 VAC, nominal 
Line Accept Value ……………………..  105 VAC, nominal 
Power Factor ……………………………   0.9 typical (line mode operation) 
 
Output Voltage …………………………  60 / 75 / 89 VAC selectable taps 
Output Voltage Tolerance ……………  +5% and –2% load regulation over input range 
Output Current …………………………  10 / 8 / 6.7 amps (into resistive load) 
Output Power ……………………………  600 watts 
Efficiency (Line Mode) …………………  Better than 90% over line voltage range, at full load 
Efficiency (Inverter Mode) …………….  Better than 85% at nominal battery, full load 
Run Time (Battery Input) ………………  Greater than 2 hours @ full load with 90A-H battery 
 
DC Input (Battery) Voltage ……………  3-battery system (18-cells):  36V nominal 
 
 
 
 
 
 4-battery system (24-cells):  48V nominal 
Low Battery Shutdown ………………..  1.75 V/cell (31.5V for 18-cells or 42.0V for 24-cells) 
Battery Acceptance Voltage ………….  3-battery system: not less than 28 volts 
 
 
 
 
 
 4-battery system: not less than 38 volts 
Battery Charge Current ………………..  5 amps @ nominal AC input 
Battery Float Voltage …………………..  2.27 V/ cell (41.0V for 18-cells or 54.6V for 24-cells) 
Temperature Compensation ………….  -0.05V/°F (-0.09V/°C) slope 
 
Protection ………………………………..  DC Input:  80A magnetic/hydraulic circuit breaker 
 
 
 
 
 
 AC Output: 20A thermal circuit breaker 
 
Operating Temperature Range ………  -40°C to +60°C  (-40°F to +140°F)  
 
 
 
 
 
 At 5% to 95% relative humidity, non-condensing 
 
Size ……………………………………….   8.6” H x 15” W x 12.5” D 
 
 
 
 
 
 (219 mm x 381 mm x 318 mm) 
 
Weight ……………………………………   xx Lbs.  (xx Kg) 
 
Status Monitoring Options …………..   StatTrak (HMS protocol) 
     HMS-to-Legacy 
converter 
allowing 
analog 
status 
monitoring 
 
 
 
 
 
 
 
 
 
 
 
29