White Rodgers 1F95-1280 Emerson Blue 12" Commercial Touchscreen Programmable Thermostat Benutzerhandbuch
Model
Programming Choices
1F95-1280
7 Day
5/1/1 Day
Non-Programmable
Big Blue Commercial Universal Thermostat
with Damper or Economizer Control and
Automatic Heat/Cool Changeover Option
Single Stage, Multi-Stage, Heat Pump
Installation and Operating Instructions
APPLICATIONS
1F95-1280
SPECIFICATIONS
Electrical Rating:
Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . mV to 30 VAC, NEC Class II, 50/60 Hz or DC
Input-Hardwire . . . . . . . . . . . . . . . . . . . . . . . . . 20 to 30 VAC
Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 .5A per terminal, 2 .5A maximum all terminals combined
Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 to 99°F (7 to 37°C)
Rated Differentials: Fast
Terminal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 .5A per terminal, 2 .5A maximum all terminals combined
Setpoint Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 to 99°F (7 to 37°C)
Rated Differentials: Fast
Slow
Heat (SS1, MS2) . . . . . . . . . . . . . . . . . . . . . . . . . . 0 .6°F 1 .5°F
Cool (SS1, MS2) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 .2°F
1 .7°F
Heat Pump (HP1, HP2) . . . . . . . . . . . . . . . . . . . . . 1 .2°F
1 .7°F
Emer Heat (HP1, HP2) . . . . . . . . . . . . . . . . . . . . . . 0 .6°F
1 .7°F
Operating Ambient . . . . . . . . . . . . . . . . . . . . . . . . . . 32°F to +105°F (0 to +41°C)
Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max .
Shipping Temperature Range . . . . . . . . . . . . . . . . . -40 to +150°F (-40 to +65°C)
Dimensions Thermostat . . . . . . . . . . . . . . . . . . . . . . 4-9/16"H x 5-13/16"W x 1-3/16"D
Operating Humidity . . . . . . . . . . . . . . . . . . . . . . . . . 90% non-condensing max .
Shipping Temperature Range . . . . . . . . . . . . . . . . . -40 to +150°F (-40 to +65°C)
Dimensions Thermostat . . . . . . . . . . . . . . . . . . . . . . 4-9/16"H x 5-13/16"W x 1-3/16"D
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
CAUTION
!
Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.
THERMOSTAT APPLICATION GUIDE
Thermostat
Configuration
Options
Thermostat
Applications
Maximum
Stages
Heat/Cool
W/ Economizer
Max. Stage
Heat/Cool
Single Stage 1
No Heat Pump (SS1)
Gas, Oil, Electric, Heat Only,
Cool Only or Heat/Cool
Systems, 2 or 3 wire Hydronic
Zone (Hot Water or Steam)
Systems, 24 Volt or Millivolt
1/1
1/2
Multi Stage 2
No Heat Pump (MS2)
2/2
2/3
Heat Pump 1
Single Stage
Compressor Heat
Pump (HP1)
Single Stage Compressor Heat
Pump Systems - up to 2 Stages
Aux ./Emergency Heat
3/1
3/2
Heat Pump 2
Two Stage or Two
Compressor Heat
Pump (HP2)
Two Stage or Two Compressor
Heat Pump systems - up to 2
Stages Aux ./Emergency Heat
4/2
4/3
ATTENTION: MERCURY NOTICE
This product does not contain mercury . However, this prod-
uct may replace a product that contains mercury .
This product does not contain mercury . However, this prod-
uct may replace a product that contains mercury .
Mercury and products containing mercury must not be
discarded in household trash . Do not touch any spilled mer-
cury . Wearing non-absorbent gloves, clean up any spilled
mercury and place in a sealed container . For proper disposal
of a product containing mercury or a sealed container of
spilled mercury, place it in a suitable shipping container .
Refer to
discarded in household trash . Do not touch any spilled mer-
cury . Wearing non-absorbent gloves, clean up any spilled
mercury and place in a sealed container . For proper disposal
of a product containing mercury or a sealed container of
spilled mercury, place it in a suitable shipping container .
Refer to
www.thermostat-recycle.org for location to send
the product containing mercury .
Index
Page
Installation
2
Wiring Diagrams
3
Thermostat Quick Reference
4
Installer Configuration Menu
5
Operating Your Thermostat
9
Programming
10
Troubleshooting
14
www .white-rodgers .com
www .emersonclimate .com
PART NO. 37-7322A
Replaces 37-6978C and 37-7292A