GE F485 Benutzerhandbuch

Seite von 8
F485 COMMUNICATIONS CONVERTER 
Page
 
4 of 8 
g
GE Multilin
 
CONNECTIONS 
 
805700A1.CDR
RS232
COMPUTER
FIBER OPTIC
RS485
POWER
POWER
9V
AC/DC
Tx
Rx
COM
RS232
FIBER
POWER JACK
The RS232 connector on the F485 converter accepts a
standard 9-pin computer cable. See wiring diagram for pin
assignments.
The fiber input/output will accept 50/125, 62.5/125 and
100/140um fiber sizes using ST terminated cables. Care
should be taken when removing the protective caps to
prevent dust from entering the connectors.
Connect the supplied power
adapter to this input if power is not
supplied via the terminals. The
power adapter steps down
120/220 VAC to 9 VAC.
RS485
The RS485 terminals accept a standard shielded twisted
pair (such as Beldon 9841) and provide connections for a
"+", "-" and a shield. The RS485 terminals have a
terminating network installed internally and therefore, no
external terminating network is required. Observe correct
polarity.
POWER TERMINALS
The power terminals accept either 9 VAC or 9 VDC to power
the F485 converter instead of using the power adapter. The
GND terminal must be connected to ground to ensure
adaquate protection against transients. Pin 4 is the main
transient ground for the converter.
GND
1
2
3
4
5
6
+
-
+
-
 
Figure 3: Connections 
CONFIGURATION 
 
The converter box is configured via two internal dip switch banks which are accessible by removing the 
converter box cover. Switches A1-A8 are used to set the baud rate for RS485 communications and 
determine whether the converter is DTE (RS232 direct) or DCE (RS232 modem). Switches B1-B6 are 
used to select the interface type. The designator for each switch is clearly marked on the printed circuit 
board. The tables shown below provide a description of each switch within the switch banks. 
 
 
 
Figure 4: Switch Locator 
 
SWITCH A (BAUD RATES) 
BAUD 
A1 
A2 
A3 
A4 
A5 
A6 
A7 
1200 
ON 
OFF 
OFF 
OFF 
OFF 
OFF 
OFF 
2400 
OFF 
ON 
OFF 
OFF 
OFF 
OFF 
OFF 
4800 
OFF 
OFF 
ON 
OFF 
OFF 
OFF 
OFF 
9600 
OFF 
OFF 
OFF 
ON 
OFF 
OFF 
OFF 
19200 
OFF 
OFF 
OFF 
OFF 
ON 
OFF 
OFF 
38400 
OFF 
OFF 
OFF 
OFF 
OFF 
ON 
OFF 
57600 
OFF 
OFF 
OFF 
OFF 
OFF 
OFF 
ON 
 
SWITCH B (CONFIGURATION)
 
CONFIGURATION 
B1 
B2 
B3 
B4 
B5 
B6 
RS232 TO RS485 
OFF 
ON 
OFF 
ON 
OFF 
OFF 
RS232 TO FIBER 
OFF 
OFF 
OFF 
OFF 
ON ON 
RS485 TO FIBER 
ON 
OFF 
ON 
OFF 
OFF 
OFF 
SWITCH A (DTE/DCE) 
MODE 
A8 
DTE 
OFF 
DCE 
ON