Utica Boilers CuB Series Installationsanweisungen

Seite von 52
16
6 - COMBUSTION AIR AND VENT PIPING- CATEGORY I (CHIMNEY VENT)
6.4 Modulating Fan
• Unit is equipped with an advanced combustion air, vent 
fl ow control system, with modulating fan and pressure 
sensor.
• Unit automatically adapts its operation to fl ue type 
and length, without requiring adjustments during 
installation or use of baffl es in combustion circuit.
• Unit consistantly and automatically regulates 
combustion air and vent fl ow according to change in 
thermal load. Combustion and heat exchange occur in 
optimum conditions. Unit’s thermal effi ciency remains 
high throughout its power range.
6.5 Venting Materials 
• See Table 3
6.2 Minimum Vent Pipe Clearance
•  Use Type B vent pipe through crawl space. Where vent 
pipe passes through combustible wall or partition, use 
ventilated metal thimble. Thimble should be 4 inches 
larger in diameter than vent pipe.
•  Boiler installed with single wall vent, must have 6” 
clearance between its surface and any combustible 
material. New Type B gas vent or fl exible liner must be 
installed in accordance with instructions furnished with 
vent. Maintain clearances as specifi ed for vent pipe.
•  Verify vent pipe is fi re-stopped where it goes through 
fl oor or ceiling. It should have approved vent cap with 
clearances from roof. If clearances are less than shown, 
have vent checked by local authorities. Figure 13, Page 
20.
•  Vent connectors serving appliances vented by natural 
draft shall not be connected into any portion of 
mechanical draft systems operating under positive 
pressure.
6.3 Removing Existing Boiler From Common 
Venting System
When an existing boiler is removed from a common
venting system, common venting system is likely to be
too large for proper venting of the appliances remaining
connected to it.
1. 
At the time of removal of an existing boiler, the 
following steps shall be followed with each appliance 
remaining connected to the common venting system 
placed in operation, while the other appliance 
remaining connected to the common venting system 
are not in operation.
2. 
Seal any unused openings in the common venting   
system.
3. 
Visually inspect the venting system for proper size and 
horizontal pitch and determine there is no blockage or 
restriction, leakage, corrosion and other defi ciencies 
which could cause an unsafe condition.
4. 
Insofar as is practical, close all building doors and 
windows and all doors between the space in which the 
appliances remaining connected to the common venting 
system are located and other spaces of the building. 
Turn on clothes dryers and any appliance not connected 
to the common venting system. Turn on any exhaust 
fans, such as range hoods and bathroom exhausts, so 
they will operate at maximum speed. Do not operate a 
summer exhaust fan. Close fi replace dampers.
5. 
Place in operation the appliance being inspected. Follow 
the lighting instructions. Adjust thermostat so appliance 
will operate continuously.
6. 
Test for spillage at the draft hood relief opening after 
5 minutes of main burner operation. Use fl ame of a 
match or candle, or smoke from a cigarette, cigar, or 
pipe. 
7. 
After it has been determined that each appliance 
remaining connected to the common venting system 
properly vents when tested as outlined above, return 
doors, windows, exhaust fans, fi replace dampers and 
any other gas-burning appliance to their previous 
conditions of  use.
8. 
Any improper operation of the common venting system 
should be corrected so the installation conforms with 
the National Fuel gas Code, ANSI Z223.1/NFPA 54, 
and/or the Natural Gas and Propane Installation Code, 
CAN/CSA B149.1.  When re-sizing any portion of the 
common venting system, the common venting system 
should be re-sized to approach the minimum size 
determined using the appropriate tables in Chapter 13 
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, 
and/or the Natural Gas and Propane Installation Code, 
CAN/CSA B149.1.
9. 
It is recommended that existing gas vents be checked 
to be sure they meet local codes.
Item
Material
Standards
Vent Pipe & Fittings
Type B Vent
UL 441, ULC S605
Masonry Chimney 
- must conform to 
proper sizing and 
materials
National Fuel 
Gas Code, ANSI 
Z223.1/NFPA 54
Combustion Air
Stainelss Steel, 
PVC, CPVC, PP, 
Aluminum
ANSI/ASTM 
D2564, ANSI/
ASTM F493, UL 
1738/ULC636-08
Table 3 - Combustion Air and Vent Pipe Fittings 
Category I (Chimney Vent)