Utica Boilers UB95M-200 Anleitung Für Quick Setup

Seite von 11
Boiler Display Key Pad Operation:
Changing a parameter
Using the six buttons on the front of the boiler (see next page for illustration) and the proper code,
the boiler can be both monitored and modified using the digital display.
Perform the following steps with the boiler powered on and in standby [STBY] mode: (STBY will
appear only momentarily followed by 0.(boiler temp), i.e. 0.120
1. Press and hold the "STEP" button.
2. While holding the "STEP" button down, press and hold the "MODE" button.
3. Hold both buttons down together for several seconds until [CODE] appears on the display.
4. Release "STEP" and "MODE" buttons. [CODE] will stay lit on the display.
NOTE: If [CODE] is not displayed after several seconds, release "STEP" and "MODE" buttons 
and press "MODE" several times to return display to [STBY].  Then repeat steps 1-4 again.
5. Press the "STEP" button once (C "xx" will appear, i.e. C 17)
6. Adjust the number displayed to [C-05] by using the "+" and "–" buttons.
7. Press the "STORE" button.
IMPORTANT: The boiler control will automatically exit [CODE] mode 
after 10 minutes of no activity.