Boiler Not Firing And:
Check For:
Step
Corrective Actions:
Control display blank
120 vac at terminals L1 and L2 of line 
voltage strip?
1
NO - Check external line switch and fuse or breaker.
2
Determine if red light on line voltage monitor is flashing 
indication fault.  If there is fault verify input voltage dial 
is properly set in accordance with steps in installation 
manual.  If fault does not clear after ten minutes replace 
line monitor.
120 vac on both sides of fuse F1? 
1
NO - Turn off power to boiler and replace fuse if 
necessary. Inspect boiler interior wiring to determine 
cause of fuse opening.
Wiring correct, in good condition, and 
securely attached?
1
Correct if needed. Replace any damaged wiring or 
components. Replace control module if problem persists.
Display first digit shows 
0; last digits show 2 or 
3-digit number (boiler 
outlet water temp.)
Room thermostat and DHW aquastat 
satisfied?
1
YES - Boiler off, no call for heat. Turn up thermostat or 
aquastat. Boiler should start.
Thermostat or aquastat calling for heat 
but boiler not firing.
1
Check voltage on both sides of low voltage fuse F3. (Turn 
OFF external power before removing cover.) If necessary, 
replace fuse. Determine reason for fuse failure if possible.
2
Check/set boiler parameters 2 and 3. Make sure space 
heat or DHW is turned on. Turn on if necessary.
3
Turn off power to boiler. Temporarily jumper low voltage 
terminal strip terminals T1 and T2 or DHW T1 and 
DHW T2. Retry. If boiler operates, check CH and DHW 
thermostat and wiring. Replace if necessary. Remove 
temporary jumper(s).
4
Turn off power to boiler. Check wiring against wiring 
diagram; verify all wiring in good condition and secure.
5
Replace wire harnesses and retry.
6
Replace control module.
Display first digit shows number from 1 to 8; last digits show 2 or 
3-digit number (boiler outlet water temp.)
1
Boiler in normal operating mode.
Display flashes “9,” then “b.” Last two digits show code number.
1
See User Interface Quick Reference and Soft Lockout
Troubleshooting for more information on soft lockout code.
Display shows U 1.25 
continuously
Transformer unplugged or not 
functional
1
Plug transformer in.
2
Replace transformer.
F3 24V 4 Amp fuse is not functional
1
Replace fuse.
9 - TROUBLESHOOTING