PAGE 2   STARTER
CONFIGURATION
START CONTROL MODE
: START RAMP 1
JOG VOLTAGE
: OFF
START RAMP #1 TYPE
: VOLTAGE
START RAMP #2 TYPE 
: OFF
KICK START
TYPE: OFF
DECELERATION
:  DISABLED
TIMED OUTPUT
TIME:  OFF
JOG, START RAMP 1, 
START RAMP 2, DUAL 
RAMP, CUSTOM ACCEL   
CURVE,START DISABLED
Range: 5 - 75% or Off
Increments 5
Options: Voltage,  Current 
               or Off
Options: Voltage, Current 
                or Off
Range: Voltage or Off
Range: Enabled or Disabled
Range: 1 - 1000 sec, OFF
Increments of 1
(Hit DOWN ARROW one time)
INITIAL VOLTAGE
#1: 20%
RAMP TIME
#1:  10 SEC.
CURRENT LIMIT
#1: 350% FLA
Range: 0 - 100%
Increments of 1
Range: 0 - 120 SEC.
Increments of 1
Range: 200 - 600%
Increments of 10
INITIAL CURRENT
#1:  200% FLA
RAMP TIME
#1: 10 SEC.
MAXIMUM CURRENT
#1: 350% FLA
Range:  0 - 300%
Increments of 1
Range: 0 - 120 SEC
Increments of 1
Range: 200-600%
Increments of 10
If
VOLTAGE
selected
these
screens
will appear.
If
CURRENT 
selected
these
screens
will appear.
INITIAL VOLTAGE
#2: 60%
RAMP TIME
#2:  10 SEC.
CURRENT LIMIT
#2: 350% FLA
Range: 0 - 100%
Increments of 1
Range: 0 - 120 SEC.
Increments of 1
Range: 200 - 600%
Increments of 10
INITIAL CURRENT
#2:  200% FLA
RAMP TIME
#2: 10 SEC.
MAXIMUM CURRENT
#2: 350% FLA
Range:  0 - 300%
Increments of 1
Range: 0 - 120 SEC
Increments of 1
Range: 200-600%
Increments of 10
If
VOLTAGE
selected
these
screens
will appear.
If
CURRENT 
selected
these
screens
will appear.
KICK START VOLTAGE
: 65%
KICK START TIME
: 0.50 SEC.
Range: 10 - 100%
Increments of 5
Range: 0.10 - 2.00
Increments of 0.10
START DECELERATION
VOLTAGE: 60%
STOP DECELERATION
VOLTAGE: 30%
DECELERATION
TIME: 5 SEC.
Range: 0 - 100%
Increments of 1
Range: 0 - 59%
Increments of 1
Range: 1 - 60
Increments of 1
RUN DELAY
TIME: 1 SEC.
AT SPEED DELAY
TIME: 1 SEC.
Range: 0 - 30 sec, OFF
Increments of 1
Range: 0 - 30 sec, OFF
Increments of 1
BYPASS PULL-IN
CURRENT: 100% FLA
Range: 90 - 300%
Increments of 1
SP.2 Starter Configuration (Setpoint Page 2)