■  Relating communication parameters
Following parameters should be set or changed if necessary.
• Communication baud rate ()... Shipment setting = : 9600bps
    Baud rate of all inverters in the network (master and slave) should be same network.
• Parity () ... Shipment setting = : Even parity
Parity of all inverters in the network (master and slave) should be same network.
• Communication error trip time() ... Shipment setting = 
Operation is continued by the last received command value in the case of a communication break-
down. To stop the operation of inverter, provide a communication time-out interval (ex. =)
to the slave inverters. The master inverter does not trip even though the communication breakdown
happens. To trip the master inverter, provide an interlock mechanism by installing a FL fault relay
point or the like from the slave side.
• Frequency point selection ()
Adjusted to the system.
See chapter “6.1 Speed proportional control” for details.
■  Setting example of parameters
Parameters relating to the master side (example)

     Master (transmission of output frequency
                       (%) (100% at FH))

      Selection of communication protocol
               (Toshiba inverter protocol)

      Communication baud rate
(ex. 19200bps)

            Parity (even parity)

      Example: Panel

  Example: Built-in potentiometer

  Communication waiting time
(ex. 30msec)
Parameters relating to the slave side (example)

 Slave (0Hz command issued in case the master inverter
fails)

   Selection of communication protocol
               (Toshiba inverter protocol)

      Communication time-out (ex. 1 second)

      Communication baud rate (same to the master side)

      Parity (same to the master side)

      Terminal block (ex. Driven by F, ST)
( Run and stop of operation is controlled with the frequency
reference value by setting the “run frequency”.)
< For speed control >

   Serial communication

?    Adjusted to the system  Point 1 setting (%)

  ?    Ditto                  Point 2 frequency (Hz)

    ?        Ditto                                    Point 2 setting (%)

  ?    Ditto                  Point 2 frequency (Hz)