1  EQUIPMENT SET-UP 
1.1 
Supplied equipment 
FS-X25 Series FieldServer
 
loaded  with  Modbus  RTU  driver,  SMT  Ethernet  driver  and  any  other  drivers  ordered.    A  default 
configuration  file  has  already  been  loaded  onto  the  FieldServer.    Check  the  Driver  Manual  and  the 
FieldServer Configuration Manual for further information on this file. 
USB Flash Drive loaded with:
 
 
 
FS-X25 Series Start-up Guide  
 
FieldServer Configuration Manual  
 
FieldServer Utilities Manual 
 
All FieldServer Driver Manuals 
 
Support Utilities 
 
Any additional folders related to special files configured for a specific FieldServer 
 
Additional components as required - See Driver Manual Supplement for details 
Accessories: 
 
7-ft Cat5 cable with RJ45 connectors at both ends (Part # FS-8915-10) 
 
Power Supply 
 
1.2 
Mounting 
The  FS-X25  Series  FieldServer  is  supplied  with  an  accessory  bag  which  allows  selection  of  adhesive  feet  (for 
standing on a shelf) or mounting plates for wall or panel mount.  A DIN Rail Mounting Kit (P/N FS-8915-28) may be 
ordered separately. 
1.3 
Wiring 
5-30VDC must be connected to the terminal block 
1.3.1  Compliance with UL Regulations  
For UL compliance, the following instructions must be met when operating the FieldServer. 
 
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature 
range. 
 
The interconnecting power connector and power cable shall: 
 
Comply with local electrical code. 
 
Be suited to the expected operating temperature range. 
 
Meet the current and voltage rating for the FieldServer/Net  
 
Furthermore, the interconnecting power cable shall: 
 
Be of length not exceeding 3.05m (118.3”) 
 
Be constructed of materials rated VW-1 or FT-1 or better. 
 
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed 
in a Restricted Access Area requiring a key or a special tool to gain access 
 
This device must not be connected to a LAN segment with outdoor wiring.