FieldServer X-25 Benutzerhandbuch

Seite von 12
FieldServer FS-X25 Start-Up Guide  
 
 
 
 
 
 
Page 6 of 12 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
CONNECTION TO THE DEVICE 
3.1 
Serial Connection 
A DB-9 cable should be connected between the Serial port on the FS-X25 and the serial port of the target  serial 
device. 
The Serial 1 port can be configured as either P1 (for RS-232 connection) or R1 (for RS-485 connection).  Likewise 
the Serial 2 port can be configured as P2 or R2.  Note that if a P1 and a R1 connection is declared, the one declared 
second will cause a configuration error on the error screen. 
 
Figure 1:  Serial Connection Ports 
3.1.1  DB-9 Pinouts for RS-232 Connection 
Used to connect to DTE type devices. 
Typical  null  modem  connection.    (Used  when 
Hardware RTS→CTS flow control is required). 
“3  wire”  null  modem  connection  (Used  when  Hardware 
RTS→CTS flow control is not required). 
 
 
The cable used (serial cross-over cable) is available at any electronics retailer/distributor.