10.0  Combustion Air And Flue Vent Exhaust
10.1 The boiler shall be a dedicated direct vent design.  The venting shall be constructed of approved 
materials and installed as per the manufactures written instructions, plan drawings and all 
applicable local code authorities.  Foam core pipe is not an approved vent material and Shall Not 
be used.  
10.2 The combustion air inlet and flue gas exhaust shall directly connect to the boiler at the locations 
labeled.  Boiler shall have the front removable jacket in place during operation.  The jacket can 
be taken off during commissioning and service per the manufactures written service and kit 
instructions
11.0  Condensate Drain
11.1 Boiler shall be equipped with a corrosion resistance non-metallic flue collector with a factory 
equipped internal drain trap.  Flue collectors manufactured out of stainless steel or cast 
aluminum are not acceptable.  The drain line external to the boiler shall be constructed of 
approved materials and installed as per the manufactures written instructions, plan drawings and 
all applicable local code authorities.
12.0  Electrical Connections
12.1 Supply voltage 120 volts 60 HZ 12 amp minimum size circuit.  The boiler shall have terminals for 
a system pump and a domestic hot water pump.  The terminals for these pumps shall be rated 
for 120 volts with a 1 amp FLA connections on 100 mbh and smaller, 10 amp FLA on 150 mbh 
and larger.
12.2 The boiler shall have Line voltage and separate Low voltage terminal strips with clearly marked 
connections.
13.0  Quality Assurance
13.1 Warranty - The Boiler shall be supplied with a written manufactures 15 year limited warranty on 
the heat exchanger and 1 year on parts and controls supplied with the boiler.
13.2 Factory Testing – The boiler shall be factory fired tested and a combustion report generated and 
included with the boiler.  
14.0  Boiler Manuals
14.1  The boiler shall be provided with a complete set of instructions and reports as follows:
Installation and Operation Manual (IOM) 
Repair Parts Manual
User’s Manual
Kit Instructions for field installed optional devices
9.0 
Low Water Cut Off
9.1  The boiler shall be equipped with a factory wired and installed probe-type low water cut off.
9.2  The Low Water Cut off shall contain power and low water condition indicating lights and a 
manually operated test button.