TR001 DEFENDER™
VGZ-026 / 052705.0
Fig. 8 - Chimney Construction Through Roof
Fig. 9 - Chimney Connection to Firebox
Through Masonry Wall
CHIMNEY CONNECTIONS continued …
MANUFACTURED CHIMNEY
REFER TO CHIMNEY AND CHIMNEY
CONNECTOR MAKER’S INSTRUCTIONS
FOR INSTALLATION AND USE.
Use only 6” diameter listed chimney UL 103
HT (U.S.) or ULC-S629 (Canada). Chimney made
to this listing is High Temperature rated to 2100
degrees Fahrenheit. Use chimney from only one
manufacturer. Never mix brands. Carefully follow
the chimney manufacturer’s stated requirements
and clearances. Use the chimney manufacturer’s
attic guards, roof supports, flashing and fire stops
when passing through a ceiling. Use a listed
thimble when passing through a combustible wall.
Do not use makeshift compromises during instal-
lation.  Never use a single-wall connection pipe
as a chimney!
When using a pre-existing chimney, have it’s
condition and installation inspected before using.
Make sure that the chimney meets all of the UL
rating requirements listed above. Be aware that not
all manufactured chimney is of the UL 103 HT
(US) or ULC-S629 (Canada) type.
NOTE: It is recommended that you contact a
licensed heating and cooling contractor (consult
your local yellow pages) for chimney installation.
Manufactured chimney with the proper re-
quired UL listing is available from most home cen-
ters, hardware stores, and HVAC supply stores.
If you have access to the internet, you may
wish to view chimney manufacturers’ informa-
tion on-line. See, www.duravent.com,
www.selkirkinc.com, or www.mtlfab.com.
VENTING TO EXISTING FIREPLACE
In some instances, people desire to convert an
existing fireplace for stove use. Usually, safe con-
nection to an existing masonry chimney requires
more work than using a prefabricated chimney. The
existing fireplace must be closed and sealed at the
damper with high-temperature caulk, ceramic
wool, or furnace cement. Prior to installation, clean
and inspect the existing flue and smoke shelf. In-
stallation should be designed so the system can be
dismantled for periodic cleaning and inspection.
Before conversion, make sure the existing chim-
Continued on next page