Utica Boilers UB95M-200 Broschüre

Seite von 2
Utica UB95M-200 Natural or Propane Gas-Fired Modulating Condensing Hot Water Boiler
Dimensions/Weights
Model
Boiler Input Rate 
(MBH) 
(1)
Heating 
Capacity 
(MBH) 
(1)(2)
Net AHRI 
Rating, Water 
(MBH) 
(1) (3)
AFUE % 
(2)
Max.
Min.
Max.
Min.
Max.
Min.
Dimensions
Width
18” 
457.2 mm
Height
39.375” 
1000.1 mm
Depth
30.875” 
784.2 mm
Flue 
Diameter
3” 
76.2 mm
Weights
Ship Wgt.
284 lbs.
128.8 kg
UB95M-200
200
80
182
73
158
63
92.5
(1) 1000 Btu/hr (British Thermal Units Per Hour)
(2) Heating Capacity and AFUE (Annual Fuel Utilization Efficiency) are based on DOE (Department of Energy) test procedures.
(3) Net AHRI Ratings based on piping and pickup allowance of 1.15.  Contact Technical Support before selecting boiler for installations having unusual piping and 
pickup requirements, such as intermittent system operation, extensive piping systems, etc.
General Information 
(See Installation, Operation and Maintenance Manual for complete instructions)
Clearances
(4) Required 
distances 
measured from 
boiler.
(5) Service, proper 
operation clearance 
recommendation.
Note: May be 
installed on 
combustible 
flooring 
(No Carpets).
Top 
Combustible Materials     
(Required) 
(4)
 
Service 
(5)
1” (26 mm)
8” (204 mm)
Left Side 
1” (26 mm)
24” (610 mm)
Right Side 
1” (26 mm)
N/A
Front 
0” (0 mm)
24” (610 mm)
Back 
6” (153 mm)
N/A
Bottom
Combustible
N/A
Combustion Air/Vent Piping
0” (0 mm)
N/A
Combustion 
Air & Vent Pipe 
Equivalent 
Length 
Min. Length
3” Pipe
15 Ft. (4.6 m)
Max. Length
100 Ft. (30.5 m)
Vent Pipe - First 2.5’ (.762 m) is Schedule 80 2” CPVC (provided), then Schedule 40 3” PVC.
Air Intake - Schedule 40 3” PVC.
Notes: 3” Pipe Min. Venting - 15 ft. equivalent length, 3” Pipe Max. Venting - 100 ft. equivalent length. 
Reduce the maximum vent length by 5’ per each 90° elbow. Refer to IOM for additional piping details.
Connections
Return/Supply Water
Gas In
Condensate Drain
1-1/4” NPT
1/2” NPT
  1/2” PVC
Note: Option of left, right, or rear exit for return plumbing and gas piping.
Electrical
120 Volts AC, 60 hertz, 1 phase, Less than 12 amps (15 amp circuit recommended) 
Water Content
2.6 Gallons
Standard 
Equipment
Boiler Control Module:  Microprocessor based Modulating Control, Hi-Limit Control.
User Display Interface: Temperature Display. Outdoor temperature sensor with cover included.
Heat Exchanger:  Cast Aluminum Monoblock.
Combustion: Modulating Automatic Gas Valve, Modulating Burner, Direct Spark Igniter, 
LP Conversion Kit included. Modulating Blower, Manual Reset Casting Temperature Switch, 
Air Proving/Blocked Vent Safety Assembly, Air Purge Vent.
Electrical:  Service Switch, Service Receptacle Outlet.
Other: Circulator (Taco 007 or Grundfos), Manual Reset Low Water Cutoff, Pressure Gauge, 30 PSI 
Safety Relief Valve, Integral Condensate Trap, Combination Painted Metal and Durable Plastic Jacket.
Options
Concentric Vent Kit (3”), AMB Multiple Boiler Control (For Multiple Boiler Applications - Includes  
outdoor reset, priority override and lead boiler run time rotation.  Available in two sizes - AMB4 and 
AMB8 to allow stage firing of up to 8 boilers).
Certifications
PN 240006151 Rev. 10/13
Contractor  
Assistance:
 800.325.5479
P.O. Box 4729 
Utica, New York 13504
tel: 315.797.1310
 
 
fax: 315.797.3762
www.uticaboilers.com
18"
front
OPENING FOR 
VENT TEE 
EXHAUST (2" CVPC)
STANDARD SUPPLY OPENING
1 1/4 NPT CONNECTIONS
PROVIDED INSIDE BOILER
CABINET. 
top
GAS SUPPLY
OPENING 1/2 NPT
(OPTIONAL) 
AIR VENT INTAKE
OPENING 2" PVC
(OPTIONAL)
WATER RETURN OPENING
1 1/4 NPT CONNECTION
(OPTIONAL)
left
WATER RETURN OPENING
1 1/4 NPT CONNECTION
(OPTIONAL)
GAS SUPPLY OPENING
1/2 NPT (OPTIONAL) 
30 7/8"
ELECTRICAL CONNECTION
FOR 120V POWER & 24 V
THERMOSTAT LEADS 
right
WATER RETURN OPENING
1 1/4 NPT CONNECTION
(OPTIONAL)
GAS SUPPLY OPENING
1/2 NPT (OPTIONAL) 
39 3/8"
OPENING FOR RELIEF 
VALVE DISCHARGE PIPE 
CONDESATE DRAIN
OPENING 1/2" PVC 
AIR VENT INTAKE OPENING
2" PVC (OPTIONAL)
back
All ratings and specifications subject to change.
50 psi MAWP