Alarm and fault messages 
4.2 Alarm and fault messages  
27 
4.2 
Alarm and fault messages 
The table below provides an overview of alarm and fault messages supplied on the inverter.  
 
Table 4-1 Alarm and fault messages 
No. Meaning 
Category  Main 
cause 
0 Manual 
Off Fault 
 
Inverter power unit is signaling 
overtemperature, stage 1 
Alarm 
Ambient temperature too high, fan defect, 
interruption in auxiliary supply to fans 
Inverter overload; i
2
-t protection 
(alarm), stage 1 
Alarm 
Parameter setting error 
Overload 
Alarm 
Parameter setting error 
12 
Inverter is in commissioning mode 
Alarm 
Parameter setting error 
14 
Fans have exceeded useful life, 
replacement required 
Alarm Replace 
fans 
33 
Inverter power unit is signaling 
overtemperature, stage 2 
Fault 
Ambient temperature too high, fan defect, 
interruption in auxiliary supply to fans 
36 
Fast Stop (1) activated, AC contactor 
defective (no checkback signal from 
contactor) 
Fault 
Fast Stop button pressed or AC contactor 
defective 
37 
Several start attempts in quick 
succession 
Fault 
DC link voltage too low, current too high, inverter 
in test mode, no Vdc setpoint 
39 
Overvoltage in the DC link (VDC
gg
Fault 
PV field is incorrectly connected 
40 
Fast Stop (2), Fast Stop via customer 
terminal block 
Fault 
Fast Stop button pressed 
43 V
CE
 protection activated 
Fault 
Defective component in the power unit 
47 
Inverter overload; i
2
-t protection 
(fault), stage 2 
Fault 
Parameter setting error 
48 
Regeneration to the DC link or 
defective AC contactor 
Fault 
Parameter setting error, AC contactor defective 
49 
Undervoltage in the DC link 
Alarm 
PV field is disconnected from the inverter 
62 
No checkback signal "Inverter ON" 
Fault 
Signal cable is not connected correctly 
63 
Direct current too high or signal cable 
is defective 
Fault 
Parameter setting error, fault at S7 analog input, 
signal cable defective 
64 
Vdc too high or  Vdc/dt too high 
Fault 
PV field is incorrectly connected 
65 
No checkback "AC contactor closed" 
or no checkback "DC contactor 
closed" 
Fault 
Contactor defective, signal cable defective 
66 
General inverter fault 
Fault 
Defective component in the power unit 
91 Fuse 
tripped Fault 
Overvoltage or short circuit has occurred, 
hardware may be defective