Alarm and fault messages 
4.2 Alarm and fault messages 
32 
 
Causes 
Inlet air temperature too high 
o
 
Air inlet to switchroom is blocked 
o
 
Air outlet from switchroom is restricted 
o
 
Ambient temperature is too high 
Replace the defective components 
Check the parameter settings 
 
Measures 
Clean or enlarge the air inlet 
Table 4-5 Faults 4 and 47 
Fault 4 (alarm): Inverter overload, I²t monitoring, stage 1 
Fault 33 (alarm): Inverter is signaling overtemperature, stage 2 
Condition 
The CU has detected a current which is higher than the 
permissible l²t limit. 
Excessive current 
o
 
Parameter setting error (CU software – 
current limit value) 
Causes 
Fault in measured-value sensing 
o
 
Parameter setting error (CU software - limit 
value I
2
t) 
 
Measures 
Adjust the parameter settings 
Table 4-6 Fault 6 
(Alarm) overload 
Condition 
The CU has detected a current which is higher than the 
selected permissible value. 
USI is defective 
AC current transformer defective 
Causes 
Parameter setting error 
 
Measures 
Adjust the parameter settings 
Table 4-7 Fault 12 
(Alarm) System is in commissioning mode 
Condition 
The CU has detected that commissioning mode is 
selected 
Causes 
The CU is in commissioning mode 
 
Measures 
Set the CU operating mode to "Reversion" 
Table 4-8 Fault 14 
(Alarm) Fan has exceeded its useful life 
Condition 
The hours counter in the CU has reached "0" (hours are 
counted backwards) 
The fan has operated for 35,000 hours since initial 
commissioning 
Causes 
The value set initially for the hours counter was too low 
Replace the fan. 
 
Measures 
Set the hours counter to 35,000 hours. 
The fans do not necessarily develop defects after working for this number of hours.