Motor components of the built-in motor and options 
 
3.3 Cooling 
 
1FW6 Built-in torque motors 
54
 
Configuration Manual, 05/2009, 6SN1197-0AD00-0BP7 
Requirements placed on the water 
The water used as the basis of the cooling medium must fulfill the following minimum 
requirements:  
●  Concentration of chloride: c < 100 mg/l 
●  Concentration of sulfate: c < 100 mg/l 
●  6.5 ≤ pH value ≤ 9.5 
Please check further requirements with the manufacturer of the anti-corrosion agent! 
Requirements placed on the anti-corrosion agent 
The anti-corrosion agent must fulfill the following requirements:  
●  The basis is ethylene glycol (also called ethanediol) 
●  The water and anti-corrosion agent do not segregate 
●  The freezing point of the water used is reduced to at least -5° C 
●  The anti-corrosion agent used must be compatible with the fittings and cooling system 
hoses used as well as the materials of the motor cooler 
Check these requirements, especially in regard to material compatibility, with the cooling unit 
manufacturer and the manufacturer of the anti-corrosion agent!  
Suitable mixture 
●  25 % - 30 % ethylene glycol (= ethanediol) 
●  The water used contains a maximum of 2 g/l dissolved mineral salt and is largely free 
from nitrates and phosphates 
Manufacturer recommendations: see appendix