Panasonic CZ-RWSY1U Installationsanweisungen

Seite von 1
Warnings about Installation of Receivers
The wireless remote uses a very weak infrared light for its signal, which can result in the 
 
z
signal not being received because of the following infl uences, so take care in where the unit is 
installed.
Inverter or rapid-start type fl uorescent lights. (Models without glow lamps)
• 
Plasma display or LCD televisions.
• 
Direct sunlight or other sources of bright light.
• 
Warnings about Installing Remote Controllers
If a remote controller is to be operated from a remote control holder that is hung on a wall, turn 
 
z
on the lights in the room as well as any electrical appliances and then check to make sure the 
air conditioner works with the remote controller in the location where it will be installed.  If it 
works, continue with installation.
If the air conditioner is to be switched from the main sensor to a remote control sensor, pay 
 
z
attention to the following when installing.
Locate where no warm or cold drafts will affect it.
• 
Locate in a place free from direct sunlight.
• 
Locate where it will not be affected by any other heat/cold source.
• 
Customer Explanation
Give the Operating Instructions and this manual to the customer after fi nishing the installation.
 
z
Use the Operating Instructions to explain to the customer how to use and care for the unit.
 
z
Things to remember when wired and wireless remotes are 
installed at the same time
Two remote controllers can be used to control the unit if the wireless remote controller is installed 
at the same time as the wired remote controller.
(Up to 2 remotes [a wireless remote controller and the wired remote controller] can be installed.)
When using 2 remotes, one or more units can be operated by the remotes.
<Note>  
When wiring remote controllers, be sure to double-check the terminal numbers of the 
indoor unit before connecting them so there are no mistakes in the wiring. (Damage will 
occur if high voltage [e.g. supply voltage] is applied.)
<Note>  
It is not possible to use more than one wireless remote controller with one indoor unit. 
(A receiver located separately can be used at the same time.)
<Note>  
If both a wireless and a wired remote controllers are to be installed and used at the 
same time, one of them must be set up as the sub remote controller.
If the wired remote controller is to be the sub remote, change the wired remote controller to the 
 
z
sub remote.
If the wireless remote controller is to be the secondary, turn the switch on the wireless receiver 
 
z
from [MAIN] to [SUB].
Accessories
No.
Parts
Q’ty
No.
Parts
Q’ty
1
Receiver
1
3
Remote control 
holder
1
4
AAA alkaline 
battery
2
5
Tapping screw
2
2
Remote 
Controller
1
6
Clamper
1
Installing the Receiver
As the receiver can only be installed in the corner where the panel wire comes out, as shown in 
Fig. A, consideration should be given to orientation when fi tting the panel to the indoor unit.
Twist off the circled area shown in Fig. A with pliers or similar.
1. 
Remove the suction grille and corner cover. (Fig. B)
2. 
Panel wire
Break off
Panel wire
Corner cover
Fig. A
Fig. B
INSTALLATION INSTRUCTIONS   
Model No. CZ-RWSY1U
Pass the wire from the wireless receiver through the grille. (Fig. C)
3. 
Fit the panel to the indoor unit and connect the wire from the receiver to the connector (CN130/WL/WHT/10P) on the indoor 
4. 
control board. (Fig. D)
After fi xing the panel in place, fi t the receiver to the panel taking care not to trap the wire from the receiver.
5. 
Clamp the receiver wire and panel wire together with the supplied clamper. (Fig. D)
6. 
Insert the receiver wire and panel wire into the wire saddles. (Fig. D)
7. 
*  Refer to the Operating Instructions supplied with the panel.
<Note 1>  Do not twist the receiver wire and the power lead-in wire together as this could lead to malfunction.
<Note 2>  If the unit power source is affected by noise, install a noise fi lter or take similar measures.
The Self-Diagnosis Function Display and What is Detected
Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote controller is connected. For 
information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to Test Run or servicing materials.
Error Detected
WL Remote Controller LED Display
Alarm Display
Run
Timer
Standby
Blinking
Communication error in the remote control 
circuit
E01–E03, E08–E14, E17, 
E18
Communication error either in the in/outdoor 
operation line or the sub-bus of the outdoor 
unit
E04–E07, E15, E16, E19–
E31
Operation of indoor protection device
P01, P09–P14
Alternately
Operation of outdoor protection device
P02–P08, P15–P31
Alternately
Error in the indoor thermistor
F01–F03, F10–F11
Alternately
Error in the outdoor thermistor
F04–F09, F12–F28
Alternately
Error in the indoor EEPROM
F29
Simultaneously
Error in the outdoor EEPROM
F30, F31
Simultaneously
Error related to the compressor
H01–H31
Error in indoor settings
L01–L03 L05–L09
Simultaneously
Error in outdoor settings
L04, L10–L31
Simultaneously
Inconsistency in Air/Heat (Including an auto-temp setting for a model without 
auto-temp settings)
Alternately
Oil Alarm (Same as operation of outdoor protection device)
Alternately
Test Run
Simultaneously
 : Off /   : On /   : Blinking (0.5 sec. intervals)
Fig. C
Fig. D
Receiver
Panel wire
Pass wire through panel.
Panel wire
Receiver wire
Clamper
CN130 [WL] 
(WHT 10P)
Wire saddle
Room Temperature Sensor Settings
Common to All Models
The indoor unit and the wireless remote controller are equipped with indoor temperature 
 
z
sensors. The sensing of indoor temperature works via one of them.
When the unit is shipped, it is set to the indoor unit, but to switch to the remote controller, press 
 
z
the sensor button (diagram at right) inside the remote controller’s cover and then check to 
make sure that Main Sensor on the LCD screen goes off.
<Note>  
Even when the sensor switch has been set to the remote controller, if the unit does 
not receive any room temperature data from the remote controller for ten minutes, it 
automatically switches back to the indoor unit sensor, so be sure to install the remote 
controller facing the receiver.
Setting Up Remote Control Functions
The functions of the wireless remote can be set on site.
(These settings are saved in nonvolatile memory in the remote controller, so even when its batteries are changed, the settings 
do not revert to the defaults.)
<Note>  
 The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel 
should make the settings.
 
Furthermore, making changes to these settings may cause actual operation to deviate from what is printed in the  
 
Operating Instructions, so be sure to explain this to the customer fully.
Making Settings (Do with unit stopped.)
Holding down the Swing/Wind Direction + OFF Timer 
1. 
 + Mode Select buttons at the same time for 4 or more seconds 
makes the display switch to the setting screen. (See Diagram Below.) 
Use the Temperature setting buttons, 
2. 
/
, to select the number of the item to be set.
Use the ON Timer buttons, 
3. 
/
, to change settings.
The settings are saved with the Once/Every Day button. When this is done, the settings display of the LCD changes from 
4. 
blinking to light.
If other settings are to be changed as well, repeat steps 2 to 4.
5. 
When all settings have been made, press the Start/Stop button.
6. 
Example: Operation mode setting screen
Item 
Number
6
1
2
3
4
Item Number & Setting Item
Setting Content
Setting when 
Shipped
1
Operation Mode
 
 
 
 
 
 
 
 
 
 
2
Flap Display
   
   
   (No Display)
             (Note 1)
3
Select Fan Speed
   
   
   (No Display)
4
Display of Set 
Temperature 
°F 
 Setting Off (Note 2) 
 °C
°F
5
Time Display
AM/PM 
 24 Hour (No Display)
AM/PM
6
Ventilation Fan 
ON/OFF
Off (No Display) 
 On
OFF 
(Note 3)
7
Cool temp Max
41 – 95°F
86°F
8
Cool temp Min
41 – 95°F
64°F
9
Heat temp Max
41 – 95°F
78°F (Note 4)
10
Heat temp Min
41 – 95°F
60°F
11
Dry temp Max
41 – 95°F
86°F
12
Dry temp Min
41 – 95°F
64°F
13
Auto temp Max
41 – 95°F
80°F
14
Auto temp Min
41 – 95°F
62°F
16
Address Setting 
Max Value
00 (ALL only) 
 01 – 31
06 (Note 5)
17
Heat temp Max 
ON/OFF
JP (Heater Max Temp Change Off)  
  EP (On)
JP
<Note 1>  While the unit is in the swinging mode (Swing/Wind Direction), the fl ap cannot be stopped in a desired position.
<Note 2>  When Setting OFF is selected, “°C” is displayed on the LCD screen.
<Note 3>  You can toggle between ON and OFF by pressing Ventilation for 4 seconds or more.
<Note 4>  If the Heater Max ON/OFF setting is not changed to EP (ON), the setting change will not be refl ected.
<Note 5>  This is the number of addresses that can be set in the address change mode. Do not set it to 07 or above.
Sensor Button
Printed in Japan
85464369523010
RECEIVER_EN.indd   1
RECEIVER_EN.indd   1
2011/10/04   12:39:26
2011/10/04   12:39:26