7.Using the UPS monitoring software and contact signal
SC05/06
SC07
SC05/06
Jumper settings
(8)
(8)
<Before change>
<After change>
SC07
● Output delay time setting for backup signal output (BU)
Continues during a power failure, and turns ON (OFF).
By setting the contact signal card’s setting switch as
shown in the table on the right, the length of time from
when the power failure occurs until the power failure signal
is output can be delayed between 0 and 3 minutes.
By setting the contact signal card’s setting switch as
shown in the table on the right, the length of time from
when the power failure occurs until the power failure signal
is output can be delayed between 0 and 3 minutes.
The power failure signal is not output if the power supply
error is resolved within the set delay time.
error is resolved within the set delay time.
● BU/BL signal reverse output setting
BU and BL signals are output in reverse.
BU-COM ON when there is a power failure
ON
1 2
3
Setting
Setting
Delay time
switch 1
switch 2
setting
OFF
OFF
0 second
(factory setting)
(factory setting)
ON
OFF
Signal output after
30 seconds
30 seconds
OFF
ON
Signal output after
60 seconds
60 seconds
ON
ON
Signal output after
180 seconds
180 seconds
AC input
ON
OFF
ON
OFF
ON
OFF
BU signal
((setting switch 3:
OFF (normal output))
((setting switch 3:
OFF (normal output))
BU signal
((setting switch 3:
ON (reverse output))
((setting switch 3:
ON (reverse output))
Backup signal output (BU) delay time setting (setting switches 1, 2)
ON
1 2
3
Setting switch 3
Backup signal output (BU)
OFF
Normal output (factory setting)
ON
Reverse output
■Jumper settings
By making jumper settings, the contact signal card SC05/06 connector pin assignments can be changed.
Turn over the contact signal card, and change all (8) of the jumper settings to "SC05/06".