Fujitsu Primecenter M1 BS2000 Benutzerhandbuch

Seite von 117
 
 75
Power Distribution
7.3.1.2
Installation options for 700 mm wide symmetrical racks
Performing the task
Ê
Install the PDU brackets as described on 
Figure 43: 5-way socket strip mounted horizontally in a 700 mm wide symmetrical rack
Ê
Screw the socket strips with 2 screws each onto the PDU brackets.
I
Installation is possible on both sides.
Rack height
Installation direction vertically 
Installation direction horizontally 
42 HU
conditionally possible
1
Max. 4x with PDU kit 3 HU
24 HU
conditionally possible
1
1
Installation is only possible on the rear side. Cable routing is restricted. Installation of cable 
arms at the same height is not possible. 
Max. 4x with PDU kit 3 HU
Table 3: Installation options for 700 mm wide symmetrical racks