5.2. 
Server Side Connection Descriptors 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify  which  port  the  device  is  connected 
to the FieldServer 
P1-P8
2
 
Baud* 
Specify baud rate 
150,  300,  1200,  2400,  4800,  9600 
(Vendor limitation) 
Parity* 
Specify parity 
None (Vendor limitation) 
Data_Bits* 
Specify data bits 
8 (Vendor limitation) 
Stop_Bits* 
Specify stop bits 
1 (Vendor limitation) 
Protocol 
Specify protocol used 
Secutron 
Handshaking*  Specify hardware handshaking 
None 
 
Example 
 
//    
Server Side Connections 
 
Connections 
Port, 
Protocol, 
Baud, 
Parity, 
Handshaking 
P1, 
Secutron, 
9600, 
None, 
None 
 
5.3. 
Server Side Node Descriptors 
Section Title 
Nodes 
Column 
Title 
Function 
Legal Values 
Node_Name 
Provide name for Node 
Up 
to 
32 
alphanumeric 
characters 
Node_ID 
Generic Node ID unique to port. Also used as panel 
number. 
0-9 
Protocol 
Specify protocol used 
Secutron 
Port 
Port to which node belongs 
P1-P8 
 
Example 
 
//    Server Side Nodes 
 
 
 
 
Nodes 
 
 
 
Node_Name, 
Node_ID, 
Protocol, 
Connection 
Node_1, 
1, 
Secutron, 
P1 
 
 
                                                      
2
 
Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 