Appendix A.  Advanced Topics 
Appendix A.1. 
Event Function or Condition Codes 
When  the  Client  driver  receives  an  event  from  the  panel,  it  stores  the  event’s  function  or  condition 
code in the Secutron_Type=function Map Descriptor’s Data Array at the device number’s offset,  
 
Example: 
Device=3 on Circuit=1 goes into alarm – the Panel reports an event with function code A (Decimal 65) 
The  Map  Descriptor  Secutron_Type=device,  Secutron_Circuit=1  will  set  a  bit  and  store  the  event 
function code A (Decimal 65) at offset 3 in the Map Descriptors’ Data Array. 
 
The  Secutron_Type=device  Map  Descriptors  will  set  a  bit  if  any  of  the  events  listed  below  occur  on 
that circuit or zone.  The bit will be cleared if the panel reports the event as cleared.  
 
The full list of event function codes are: 
 
ASCII value 
Decimal 
Meaning 
65 
Alarm 
66 
Bypass 
67 
Comlink 
68 
Duplicate Addressable Device 
69 
Maintenance Alert 
71 
Ground Fault 
72 
Hot Key Pressed 
73 
Illegal Addressable Device 
74 
Switch 
77 
Missing Addressable Device 
78 
Non-Fire/Non-Reporting 
80 
Pull Station Alarm 
81 
Releaser Abort 
82 
Releaser Halt 
83 
Supervisory 
84 
Trouble or Parameter Change 
85 
Wrong Device Type 
87 
Waterflow Alarm