1 Hardware and Engineering
Setup
The XC600 PLC has a modular design. The basic unit consisting of 
the base, power supply, CPU and operator modules can be 
expanded with function modules for communication. Modules for 
the standard PROFIBUS-DP and CANopen networks are therefore 
provided for this purpose. They provide the controller with access 
to the I/O devices that log process data signals and control 
actuators. 
The process signals can also be connected locally with XI/ON input 
and output modules. This requires the use of the power supply 
module with the integrated XI/ON interface and the base module 
with the XI/ON adapter.
A module consists of a circuit board that is embedded in a frame. 
The special frame design makes it possible to stack the modules 
together, thus allowing compact functional units to be combined 
to suit the requirements of the task at hand.
The circuit boards of the individual function modules meet the 
requirements of the PC/104+ specification. In addition to dimen-
sions, the specifications also stipulate the requirements of the 
PC/104+ bus that connects the modules. This bus also carries the 
power supplies from the power supply module to the individual 
function modules.
A configuration containing XI/ON input/output modules must 
always include theXC-ADP-XION base module with the 
XC-POW50-XION-UPS power supply module. The power supply 
module adapts the PC/104+ bus to the XI/ON module bus using 
the XI/ON interface. This bus is connected out from the base 
module. The adapter on the base module provides the interface to 
the XI/ON modules. The 24 V DC field power supply of the XI/ON 
modules is also connected to the base module.
XC600
Base module
Power supply 
module
Without XI/ON 
connection
XC-ADP
XC-POW50-UPS
With XI/ON connection
XC-ADP-XION
XC-POW50-XION-UPS
Figure 1:
Order of modules
XC-ADP/XC-ADP-XION base module
XC-POW50-UPS/XC-POW50-XION-UPS power supply module
cdXC-NET-DP-M PROFIBUS-DP module*
or XC-NET-CAN CANopen module *
XC-CPU601-ExM CPU module*
XC-SYS1 operator module*
* Function modules