Burnham Bottom Blowdown Tank Merkblatt

Seite von 2
Bottom Blowdown Tank
Boiler Pressure  
PSIG
Blow-off Line Pipe Size
Vent Pipe Size
Outlet Pipe Size
Diameter of Tank
Height of Tank
100
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
2-1/2"
3"
3-1/2"
4"
5"
6"
3"
3"
4"
5"
6"
6"
20"
24"
30"
42"
48"
54"
3'6"
4'0"
4'2"
4'0"
4'6"
6'0"
150
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
3-1/2"
4"
5"
6"
8"
3"
3-1/2"
4"
5"
6"
8"
20"
24"
36"
42"
54"
60"
3'6"
5'0"
5'0"
5'0"
5'6"
6'0"
200
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
4"
5"
6"
8"
8"
3"
4"
5"
6"
8"
8"
20"
30"
36"
42"
48"
60"
4'3"
4'6"
5'0"
6'0"
7'3"
7'0"
250
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3-1/2"
4"
5"
6"
8"
10"
3"
4"
5"
6"
8"
10"
24"
30"
42"
48"
54"
60"
4'0"
4'6"
4'6"
5'0"
7'0"
7'2"
300
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3-1/2"
5"
6"
8"
8"
10"
3-1/2"
5"
6"
8"
8"
10"
24"
30"
42"
48"
60"
66"
4'6"
5'6"
5'0"
5'6"
6'3"
7'8"
350
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
4"
5"
6"
8"
10"
10"
4"
5"
6"
8"
8"
10"
24"
30"
42"
48"
60"
72"
5'0"
5'6"
5'6"
6'2"
6'10"
7'0"
400
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
4"
5"
6"
8"
10"
10"
4"
5"
6"
8"
8"
10"
24"
30"
42"
48"
66"
72"
5'6"
6'0"
6'0"
6'4"
6'0"
8'0"
Boiler Rating  
HP
Cu. Ft.
Minimum Size Tank
Gallons
2 – 20
3.5
18" diameter x 24"
26.4
21 – 50
7.7
24" diameter x 30"
59
51 – 100
14.7
30" diameter x 36"
110
101 – 200
21.6
36" diameter x 36"
160
201 – 400
24.8
36" diameter x 42"
185
401 – 800
39.5
42" diameter x 48"
288
801 – 1000
63.0
48" diameter x 60"
470
©2012 Burnham Commercial
P.O. Box 3939  
  Lancaster, PA 17604
Phone: 888.791.3790  
  Fax: 717.293.5803
www.burnhamcommercial.com
Form No. PL81465601008-12/12-1Mc