All installations and services must be performed by qualified service personnel.
 
 13
If the combustion air passageway cannot terminate outside of the skirting or 
enclosure, a permanent opening with a minimum of 50 square inches of 
unobstructed infiltration (free area) for ventilation air must be provided for 
adequate combustion.  This permanent opening must be located no less than 12 
inches from the bottom of the enclosure or skirting.
  
 
Figure 3 
 
Slit the corners of feeder duct down to the top of the top panel.  If metal projects 
more than 1 inch above the top panel, trim the flanges down to 1 inch.  While pulling 
the top of the distribution duct up with one hand, bend down each side of the feeder 
duct tightly to the top panel with the other hand.  This assures a tight connection 
between the top panel and the feeder duct and that the distribution duct will be full 
size.  Use high temperature tape and/or high temperature silicone caulking on all 
joints and seams to minimize air leakage.  Secure the top panel to the floor with two 
screws in the front flange. 
 
2.  Cottage Base Model: O1COT-BASE 
 
The O1COT-BASE cottage base (Figure 1B) is required for a freestanding cottage 
base installation.  The cottage base is designed to permit the installation of a 6-inch x 
14-inch register in each of the two side panels and the front panel.